Honeywell MS-9600LS Smoke Alarm User Manual


 
36 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Product Description Accessories
ANN-LED Board Layout and Connection to FACP
Figure 1.13 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-RLY Annunciator Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
Specifications
Operating Voltage: 24 VDC
Max. Current:
Alarm: 75 mA
Standby: 15 mA
Relay Contact Ratings
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Operating Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
For indoor use in a dry location only
TB1
J1
SW1
JP2
ANN-BUS
1 2 3 4 5 6 7 8
TB3
JP5
TB4
JP8
TB5
TB6
TB1
+ - + - + - + -
A B
Figure 1.13 ANN-LED Connection to FACP
FACP
ANN-LED
ANN-BUS/
ACS BUS
+24 VDC
-24 VDC
9600lstoled.wmf
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS (ID#)
Address DIP switch