Honeywell M9491 Burner User Manual


 
4074EED
RESISTOR SELECTION CHART FOR
4-20
mA
MIINIMUM
OUTPUT
VOLTAGE
REQUIRED
MOTORS
(Vdc)b
RESISTOR (A)
(Ohms) Part No.
1
1.7 237 80213QCDHA
2 2.0
150
802139BFAA
:
2.3 2.7 124 113 802139BCEA 802139BBDA
5
3.0
105a
-
6
3.3 97.6”
-
CHECKOUT
After installation and linkage adjustment, check the entire
motor and control hookup to ensure that-
*
The motor operates the damper or valve properly.
l The motor responds properly to the controller.
Inspect the motor, linkage, and valve or damper to see
that all mechanical connections are correct and secure. In
damper installations, the
pushrod
should not extend more
than a few inches past the ball joints. Check to see that
there is adequate clearance for the linkage to move
through its stroke without binding or striking other objects.
Check to see that cams operate the auxiliary switches,
if used, at the desired point of motor rotation.
a
Not part of this kit, obtain separately.
b
These values represent the controller output voltage
required to drive the motors.
NOTE: Motors are shipped in the fully closed position (the
limit of counterclockwise rotation as viewed from the
power end of the motor) with the stroke set at
90”.
SERIES 90 MOTORS OPERATION CHECK WITH MODUTROL MOTOR DISCONNECTED FROM CONTROLLER
STEP ACTION
RESPONSE
IF NO OR LIMITED RESPONSE
1.
Apply 24
Vaca.
None.
-
2.
Open terminal B and short W to R. Motor drives closed. Proceed to Step 6.
3.
Open terminal W and short B to R. Motor drives open.
Proceed to Step 6.
4.
Connect terminals
R
to B to W.
Motor must drive to
Mid-
Proceed to Step 6.
position.
5.
Remove jumpers from
R,
B, and W.
17 to 20 Vdc.
No voltage or out of range. Proceed
Check voltage between B and R,
to Step 7.
and W and R.
6.
Motor does not drive.
Motor is defective.
Replace motor.
7.
Voltage out of range.
Motor printed wiring board
Replace motor.
is defective.
8.
Disconnect 24
Vat.
Spring return motors return
Spring mechanism defective
to their normal mechanical -replace motor.
position.
NOTES:
a
Ensure motor transformer is sized properly. If a common transformer is used to power multiple motors, ensure power
input is in phase with all motors.
b
Motors may operate in Series 90 or two-position control applications. However, checking voltage between terminals
R
to B and R to W is necessary to confirm proper operation in electronic (W973, 4 to 20
mA
etc.) applications.
DAMPER APPLICATION
1. Turn off power and remove wiring from the old
actuator.
2. Remove crank arm from shaft of old actuator and
remove the old actuator.
3.
Checkto
see
whether or
not the mounting bracket is
needed.
lf
the linkage can reach the lowershaft position of
the new actuator and if the crank arm has clearance for the
needed rotation, then the bracket is not needed. Use
220738A Adapter Bracket or 221455A crank arm if crank
arm must rotate through the bottom plane of the motor (for
damper applications).
4a.If
the bracket is not needed, mount the new actuator
directly to the equipment and refer to the INSTALLATION,
SETTlNGS&ADJUSTMENTS,andCHECKOUTsections
of these instructions as needed.
4b.ffthe
bracket is needed,
referto
the Adapter Bracket
sections and see Fig. 3 as well as the INSTALLATION,
SETTINGS &ADJUSTMENTS, and
CHECKOUTsections
of these instructions.
5. Use old mounting bolts to mount the new actuator.
6. Mountthedampercrankarmandlinkagetotheshaft
of the new actuator.
8. Use the CHECKOUT procedures to test the proper
adjustment of the crank arm and linkage.
.
VALVE APPLICATION
When installing a M9484, M9494 motor in a valve ap-
plication which has a
QlOO,
Q601 or
0618
it will be
necessary to use the 220738A Adapter Bracket provided
to
raisethe
motorshafttothesame height asthatof
theold
motor. Ensure motor stroke is
160”
to operate Honeywell
V5011
two-way or
V5013
three-way valves.
Honeywell
Inc.
International Sates Offices
in all
principal cities of the world. Manufacturing in
U.S.A.:
1885 Douglas Drive N. Australia, Canada, Finland, Franc%, Germany, Japan, Mexico, Netherlands,
Golden Valley, MN 55422-4386 Spain, Taiwan, United Kingdom, U.S.A.
@
CANADA: 740 Ellesmere Road
Lz3
Scarborough, Ontario Ml P
2V9
PRINTED IN U.S.A.
QUALITY IS KEY