10 Relay Module (optional)
The AirAlert
TM
96d-RM8 relay module acts as an output
to the AirAlert
TM
96d controller. The relay module
provides eight programmable relays for the activation
of ventilation and audible/visual alarm output devices
at programmable alarm levels. Since the relay module
is an output to the controller, it can be located at any
point within the gas detection network.
AirAlert
TM
96d-RM8 Features:
Fully compatible with the AirAlert
TM
96d controller
Equipped with 8 programmable DPDT relays
RS-485 daisy chain installation
LED visual indication status of each relay
Specifications
Power Requirements
17 to 27 Vdc, 250 mA
Operating Temperature Range
32°F to 100°F
Operating Humidity Range
0 to 95% RH (non-condensing)
Outputs
8 DPDT relays; 5A
30 Vdc or 250 Vac (resistive load)
Maximum Distance between Relay Module
and Controller
2,000 feet
Enclosure
NEMA 4x, cast aluminium #A356.0T6
Dimensions
9.50” (W) x 14.00” (H) x 3.50” (D)
Weight
11.4 lbs (5.2 kg)
LEDs
Two LEDs indicate the status of the relay module.
The Power LED (green) indicates that the relay
module is powered on. The Tx Modbus LED blinks
when there is a data transfer between the relay
module and the controller. If the communication
breaks down, that LED will turn off.
Figure 10. AirAlert
TM
96d-RM8
Dip Switches
The DIP switches are used to change the relay module
addresses. The address ranges available begin at 81.
Position of the DIP switches
Modbus
address
Dip 1 Dip2 Dip 3 Dip 4
081
Off
Off Off Off
082
On
Off Off Off
083
Off
On Off Off
084
On
On Off Off
085
Off
Off On Off
086
On
Off On Off
087
Off
On On Off
088
On
On On Off
089
Off
Off Off On
090
On
Off Off On
091
Off
On Off On
092
On
On Off On
093
Off
Off On On
094
On
Off On On
095
Off
On On On
096
On
On On On