Honeywell 96D Carbon Monoxide Alarm User Manual


 
Manning AirAlert-96d Gas Monitor 19073 AIRALERT96D 05/2006 Prelim REVC Copyright © 2006 Honeywell Analytics. All Rights Reserved. 13
7 Configuration continued
Display (programming the label)
The “label” is a descriptive message of up to 20
characters appearing on the display for a network
component. It applies to sensors, relay modules and
annuciators panels and is located on the first line of
the display. For a MODBUS sensor, the default label
is composed of the name of the sensor or network
component followed by the sensor type (if
applicable) and the component address.
Alarm A (Programming Warning Levels)
The MAX value is the level at which Alarm A (Warn) is
activated (set). The MIN value is the level at which
Alarm A (Warn) is deactivated (rest).
Alarm B (Programming Alarm Levels)
The MAX value is the level at which Alarm B (Alarm)
is activated (set). The MIN value is the level at which
Alarm B (Alarm) is deactivated (rest).
Alarm C (Programming High Alarm Levels)
The MAX value is the level at which Alarm C (High
Alarm) is activated (set). The MIN value is the level at
which Alarm C (High Alarm) is deactivated (reset).
Erase Current Tx (Erase Current Displayed
Tx Configuration)
Groups (Programming Groups of Sensors)
The programming of groups of sensors serves to
combine several units in order to be able to take
actions (events) based on a series of units rather
than each individual one at a time. It is possible to
program 126 distinct groups. Another group (GrAII)
contains all the sensors within a network by default.
A group is comprised of a stack containing the
address of each sensor included in the group. The
pointer is represented in the stack by the flashing
triangular brackets < >. The address within these
brackets is editable. When the Enter key is pressed,
the address begins to flash, and the brackets stop
flashing. The address can then be modified using the
up and down arrows. The address of each sensor
programmed in 1. INFO Tx
TxTx
Tx is available. The <DEL>
function can be used to delete a particular sensor.
The <END> indicator represents the bottom of the
stack. To add a sensor to the group, simply move the
pointer towards that position and replace <END>
with the address of the new sensor. The end of the
stack will then move over one position.
The EMPTY ALL GROUPS function deletes all groups
programmed in the AirAlert
TM
96d controller.
1. Tx Info 001
-Alarm C-
MIN MAX
240.0ppm 250.0ppm
1. Tx Info 001
-Alarm B-
MIN MAX
140.0ppm 150.0ppm
1. Tx Info 001
-Alarm A-
MIN MAX
45.0ppm 50.0ppm
1. Tx Info 001
-Display-
edit (20 char. Max)
Engine Room
1. Tx Info 001
Erase current Tx
2. Group 001
[001] [004] <end> [---]
[---] [---] [---] [---]
empty all groups