Heatcraft Refrigeration Products CH-B-01 Humidifier User Manual


 
7
Model TL
Thin Profile Electric Defrost Reach In Unit Cooler
APPLICATION
The TL low temperature unit cooler has a completely
automatic defrost system. Mounted in the top of a
refrigerator, its extremely compact cabinet makes it possible
to utilize the entire top shelf area for storage. Having a
normal operating range of +15°F to -20°F, this unit is ideally
suited for such applications as commercial freezers, ice cream
boxes, and bakery freezers.
FEATURES
Electric defrost insures positive heat source.
Built-in fan delay allows coil to be chilled before returning
to the normal cooling cycle.
Defrost terminates on coil temperature eliminating
excessive defrost period.
Defrost termination and fan delay control, terminal block
and junction box are mounted inside the cabinet.
Textured aluminum cabinet.
Molded Lexan
®
fan guards - safety approved.
Knockouts provided on sides for electrical connections -
opening in rear for coil connections.
Stainless steel screws.
Motors are thermally protected and permanently lubricated.
Internal junction box for electrical connection.
Plate type aluminum fins with full collars - copper tubes.
Coils are dehydrated and sealed.
Easy to install and maintain.
UL listed for the United States and Canada; UL classified to
NSF standards.
BTUH 10˚F TD
MOTOR DATA HEATER DATA
CONNECTIONS (INCHES)
APPROX.
MODEL +20˚F -10˚F 115/1/60 208-230/1/60 115/1/60 208-230/1/60 COIL SHIP WT.
TL SST SST
CFM QTY
TOTALFLA TOTALFLA
WATTS AMPS AMPS INLET
SUCTION
DRAIN (LBS.)
09 1050 900 110 1 0.8 0.4 475 4.1 2.1
1
/2FN
3
/8ID
1
/2OD 14
12 1380 1200 210 2 1.6 0.8 600 5.2 2.6
1
/2FN
3
/8ID
1
/2OD 19
16 1780 1600 210 2 1.6 0.8 700 6.1 3.0
1
/2FN
1
/2ID
1
/2OD 23
21 2400 2100 240 1 1.0 0.5 1100 9.6 4.8
1
/2FN
1
/2ID
1
/2OD 24
28 3200 2800 335 3 ----- 1.2 1430 ----- 5.7
1
/2FN
5
/8ID
1
/2OD 27
*35 4000 3500 420 2 ----- 1.0 1600 ----- 7.0
1
/2FN
5
/8ID
1
/2OD 38
*53 6100 5300 595 3 ----- 1.5 1950 ----- 8.5
1
/2FN
7
/8ID
1
/2OD 53
Performance/Electrical Data
* These models use external equalized expansion valves.
DIMENSIONAL DATA
MODEL DIMENSIONS (INCHES)
TL A B C D E F H J K L M N P W
09 14
5
/8 14
15
/16 13
1
/2 10
1
/2 11
3
/8 4
1
/2 8
7
/8 2
1
/2
15
/16 4
3
/8 --- 1 16
1
/2
12 18
5
/8 14
15
/16 13
1
/2 10
1
/8 10
1
/4 4
1
/2 8
3
/8 9
1
/2
15
/16 4
3
/8 --- 1 20
1
/2
16 22
1
/8 15
15
/16 14
1
/2 11
1
/8 12 4
1
/2 9
3
/8 11
1
/4
15
/16 4
3
/8 --- 1 24
21 22
1
/8 16
1
/2
15
/16 16
1
/2 14
1
/2 18
7
/8 6
3
/4 11
7
/8 17
1
/4
15
/16 4
3
/8 --- 1
1
/2 24
28 29
3
/4 15
15
/16 14
1
/2 13 20
3
/4 6
3
/4 9
3
/4 9
7
/8
15
/16 4
3
/8 --- 1 31
5
/8
35 35
3
/4 16
1
/2 1
5
/16 16
1
/2 14
1
/2 33
1
/4 6
3
/4 11
5
/8 18
3
/8 1
5
/16 65
1
/8 1
1
/2 38
3
/8
53 46
1
/2 16
1
/2 1
1
/8 16
1
/2 14
1
/2 44 6
3
/4 11
5
/8 30
3
/8 1
1
/2 65
1
/8 1
1
/2 49
1
/8
NOMENCLATURE
Vintage
A = 115/1/60
B =
208-230/1/60
TL = Thin
Profile
Electric
Defrost
Size
TL 12 A F