Heat & Glo LifeStyle CRESCENT II Indoor Fireplace User Manual


 
Heat & Glo • Crescent II • 2083-902 Rev. N • 7/0916
2. Top Vent - Vertical Termination
No Elbow
Figure 5.6
Figure 5.7
Two Elbows
V
1
H
1
V
1
V
2
V
1
= 45 ft. Max. (13.7 m)
RESTRICTOR
PLATE
Note: For vertical venting of 8 feet or higher,
the restrictor plate should be used. The
restrictor is shipped in bottom of replace
(secured on right side with a tie strap). Insert
the restrictor plate in center of ue. Once
installed in center of ue turn the restrictor
plate so it sits on top of rebox.
V
1
H
1
Maximum V
2
V1 + V2 Minimum
One Elbow 2 ft 610 mm * * *
6 in 152 mm 2 ft 610 mm * * *
1 1/2 ft 457 mm 3 ft 914 mm * * *
2 1/2 ft 762 mm 5 ft 1.5 m * * *
3 1/2 ft 1067 mm 7 ft 2.1 m * * *
4 1/2 ft 1.4 m 15 ft 4.6 m * * *
V
1
+ V
2
+ H
1
= 38 ft (11.6 m) Max.
*No speci c restrictions on this value EXCEPT
V
1
+ V
2
+ H
1
cannot exceed 38 ft (11.6 m)