Heat & Glo LifeStyle CRESCENT II Indoor Fireplace User Manual


 
Heat & Glo • Crescent II • 2083-902 Rev. N • 7/09 11
A. Vent Termination Minimum Clearances
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as
speci ed.
Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials
away from vent pipe may cause re.
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 4.1
Figure 4.2 Minimum height from roof to lowest discharge
opening
4
4
Termination Locations
Measure horizontal clearances from this surface.
Measure vertical clearances from this surface.
Figure 4.2 speci es minimum vent heights for various
pitched roofs.
(See Figure 4.4 for speci c clearances)
* 3 foot minimum in snow regions
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
WARNING
Fire Risk.
Explosion Risk.
Inspect external vent cap regularly.
Ensure no debris blocks cap.
• Combustible materials blocking cap may
ignite.
• Restricted air ow affects burner operation.
WARNING
Figure 4.3 Staggered Termination Caps
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Termination
Cap **
A*
*
If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative capcover.
**
In a staggered installation with both gas and wood terminations, the
wood termination cap must be higher than the gas termination cap.
AB
6in.(minimum)upto20in.
152 mm/508 mm
18 in. minimum
457 mm
20 in. and over 0 in. minimum
Î