Heat & Glo • Cerona-36, Cerona-42 • 2106-900 Rev. A • 6/06
19
C. Vertical Penetration Framing
Installing the Ceiling Firestop
• Frame an opening 10 inches by 10 inch-
es whenever the vent system pene-
trates a ceiling/floor (see Figure 6.3).
• Frame the area with the same sized lum-
ber as used in ceiling/floor joist.
• When installing a top vent vertical termi-
nation appliance the hole should be di-
rectly above the appliance, unless the
flue is offset.
• Do not pack insulation around the vent.
Insulation must be kept away from the
pipe.
Figure 6.3
ATTIC
ABOVE
A
B
WARNING
Fire Hazard
Keep loose materials or
blown insulation from touch-
ing the vent pipe.
Installing Attic Shield
Note: An additional ceiling firestop is not
required if attic shield is used.
• Frame opening for attic shield.
• Attic shield may be installed above or
below ceiling (see Figure 6.4).
• Secure with three fasteners on each
side.
• Fold tabs at top of attic shield in toward
vent pipe. Tabs must keep vent pipe
centered within shield.
• Field construct additional shield height
if insulation is deeper than height of at-
tic shield.
Figure 6.4 Installing the Attic Shield
• National building codes recommend us-
ing attic shield to keep loose materials/
blown insulation from contacting vent.
• Hearth & Home Technologies requires
the use of an attic shield.
A B
10 in. 10 in.
DVP
PIPE
3 FASTENERS
PER SIDE
BEND TABS IN
AROUND PIPE
ATTIC SHIELD INSTALLED
BELOW CEILIN
G
ATTIC SHIELD INSTALLED
ABOVE CEILING