Heat & Glo LifeStyle BAY-38HV Indoor Fireplace User Manual


 
20
3. Install Support Brackets
For Horizontal Runs - The vent system must be supported
every five (5) feet of horizontal run by a horizontal pipe support.
To install support brackets for horizontal runs:
 Place the pipe supports around the vent pipe.
 Nail the pipe supports to the framing members.
1 INCH MIN.
(25.4mm)
FLUE
OUTLET
WALL BRACKET
WALL STUD
8 FT.
(2.4mm)
For Vertical Runs - The vent system must be supported
every eight (8) feet (2.4m) above the fireplace flue outlet by
wall brackets.
To install support brackets for vertical runs:
Attach wall brackets to the vent pipe and secure the wall
bracket to the framing members with nails or screws.
4. Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.
NOTE: Model SLK-01TRD does not need an exterior
firestop on an exterior combustible wall. The firestop is
built into the cap.
To install firestops for horizontal runs that pass through
either interior or exterior walls:
Cut a 10 X 10 (254mm X 254mm) hole through the wall.
NOTE: The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.
Position the firestops on both sides of the hole previ-
ously cut and secure the firestops with nails or screws.
The heat shields of the firestops MUST BE placed to-
wards the top of the hole.
Continue the vent run through the firestops.
Figure 18. Hole and Vent Pipe
Figure 19. Heat Shield, Interior & Exterior Firestops
VENT PIPE
1" (25.4 mm)
10"
(254mm)
10"
(254mm)
TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT
EXTERIOR
FIRESTOP
INTERIOR
FIRESTOP
HEAT SHIELD
Figure 17. Installing Support Brackets
NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.