Heat & Glo LifeStyle 2137-900 Indoor Fireplace User Manual


 
27
Heat & Glo • Soho24B • 2137-900 Rev. P • 8/12
Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield restop is
required on the exterior side of a combustible wall.
K. Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping ue section of
the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of ue telescoping
section is required.
Failure to maintain overlap may cause overheating and
re.
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
• When installing a horizontal termination cap, follow
the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require
installation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a ashing kit
and HRC caps are available. When penetrating a brick
wall, a brick extension kit is available for framing the brick.
Figure 8.17 Venting through the wall
INTERIOR
HEAT SHIELD OR
EXTENDED
HEAT SHIELD
WALL SHIELD
FIRESTOP
HEAT SHIELD
1-1/2 IN. (38 MM) MIN.
OVERLAP
SHEATHING
SLIP SECTION
CAN BE EXTENDED
INNER VENT
OUTER VENT
EXTERIOR