Heat & Glo LifeStyle 2137-900 Indoor Fireplace User Manual


 
Heat & Glo • Soho24B • 2137-900 Rev. P • 8/12
12
Figure 5.3
Figure 5.4
1. Top Vent - Horizontal Termination
One Elbow
Two Elbows
V
1
Minimum H
1
Maximum
Elbow only 1-1/2 ft. 457 mm
1 ft. 305 mm 2-1/2 ft. 762 mm
1-1/2 ft. 457 mm 3-1/2 ft. 1.1 m
2-1/2 ft. 762 mm 5-1/2 ft. 1.7 m
3-1/2 ft. 1.1 m 7-1/2 ft. 2.3 m
4-1/2 ft. 1.4 m 15-1/2 ft. 4.7 m
V
1
+ H
1
= 39 ft. (11.9 m) Maximum
H
1
= 15-1/2 ft. (4.7 m) Maximum
V
1
Minimum H
1
+ H
2
Maximum
2 - 90º elbows
back to back
Cannot do
6 in 152 mm 1 1/2 ft. 457 mm
1-1/2 ft. 457 mm 2-1/2 ft. 762 mm
2-1/2 ft. 762 mm 4-1/2 ft. 1.4 m
3-1/2 ft. 1.1 m 6-1/2 ft. 1.9 m
5-1/2 ft. 1.7 m 15-1/2 ft. 4.7 m
V
1
+ H
1
+ H
2
= 48 ft. (14.6 m) Maximum
H
1
+ H
2
= 15-1/2 ft. (4.7 m) Maximum
D. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
ALWAYS maintain speci ed clearances around venting and restop systems.
Install wall shield and ceiling restops as speci ed.
Failure to keep insulation or other material away from vent pipe may cause re.
WARNING
H
1
V
1
INSTALLED
HORIZONTALLY
H
1
H
2
V
1