Heat Controller 7602-443 Thermostat User Manual


 
7
Heat Controller, Inc. 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Installation Manual
THERMOSTAT
CONFIGURATION
PROGRAMMABLE
NON PROGRAMMABLE
NIGHT SETBACK
SELECT OPTION
PREVIOUS SAVE
INSTALLER SETTINGS
THERMOSTAT CONFIG
SYSTEM CONFIG
ACCESSORY CONFIG
INPUT DEALER INFO
HUMIDITY CONFIG
TEMPERATURE ALGORITHM
DEMAND REDUCTION CNFG
SERVICE MODE
RESTORY DEFAULTS
ATC32U01
SELECT OPTION
PREVIOUS
AIRFLOW SELECTION
CFM
HEAT STAGE 1 600
HEAT STAGE 2 750
AUXILIARY HEAT 850
EMERGENCY HEAT 850
COOL STAGE 1 525
COOL STAGE 2 700
COOL DEHUMID 1 425
COOL DEHUMID 2 550
CONTINUOUS FAN 350
HEAT OFF DELAY 60
COOL OFF DELAY 30
PREVIOUS NEXT
NOTE: “Motorized Valve” used here refers to a two-position
motorized water valve, not to be confused with the modulating
motorized water valve found in the LOOP CONFIG.
2.2.3 PROGRAMMING
Adjust the Programming options using the up/down arrow
buttons. Press the center button to save changes.
• Programmable (default) – enables 7-day
programming
• Non-Programmable – disables 7-day programming
• Night Setback – enables night setback
programming
NOTE: When the thermostat is con gured for non-
programmable mode, the Display Date and Time setting
defaults to NO.
3.0 System Con guration
Use the System Con guration option on the start-up screen
to adjust critical equipment settings.
The System Con guration information will be automatically
obtained from each communicating control in the system.
Note 1: The Air ow Selection menu (section 3.1) will not be
present if the connected communicating control is con gured
for No Blower.
Note 2: The Valve Con guration menu (section 3.4) will
not be present if the connected communicating control is
con gured for No Loop Con guration (OTHER).
3.1 AIRFLOW SELECTION
Adjust the air ow settings for each system operating mode
using the up/down arrow buttons. Press the center button to
select each item.
Air ow Settings (defaults stored in control) -
valid range: obtained from control (in 25 CFM
increments)
Blower Off Delay (default 60 seconds) – valid
range: 0 to 255 seconds (in 5 second increments)
NOTE 1: The Air ow Settings will only be present if the
connected communicating control is con gured for ECM
blower.
NOTE 2: If multiple units are connected to one thermostat,
refer to section 3.5 for unit selection.
3.2 OPTION SELECTION
This option allows the con guration of heat pump options to
be modi ed.
Adjust the Option settings using the up/down arrow buttons.
Press the center button to select each item.
Motorized Valve (defaults stored in control)
valid range: Off, On
“On” delays compressor start until the valve is fully open.
SYSTEM CONFIGURATION
AIRFLOW SELECTION
OPTION SELECTION
UNIT CONFIG HE024
PUMP CONFIGURATION
SELECT OPTION
PREVIOUS SAVE