Heat Controller 7602-443 Thermostat User Manual


 
10
Installation Manual 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Heat Controller, Inc.
4.0 Accessory Con guration
A service message will ash at the top of the Main screen
when a service timer expires to alert the user that it is time to
service these options. Refer to DXM2 AOM for instructions on
con guring DIP switches to con gure accessories. Follow the
instructions below to set service timers.
5.0 Input Dealer Information
Enter/edit the Dealer Information settings, including Brand
Name, Model Number, Serial Number, Contractor Name, and
Contractor Phone number, using the up/down arrow buttons.
Press the center button to save changes.
4.1 AIR FILTER
This feature displays an alert to remind the user to change
the air lter after the selected time has passed.
Adjust the Air Filter Reminder settings using the up/down
arrow buttons. Press the center button to save changes.
Cumulative Run Time (default Off) – valid range:
Off, 400 to 3600 hours (in 100 hour increments)
Calendar Time (default Off) – valid range: Off, 3
to 48 months (in 3 month increments)
4.2 HUMIDIFIER
This feature displays an alert to remind the user to change
the humidi er pad after the selected time has passed.
Adjust the Humidi er Reminder settings using the up/down
arrow buttons. Press the center button to save changes.
Cumulative Run Time (default Off) – valid range:
Off, 400 to 3600 hours (in 100 hour increments)
Calendar Time (default Off) – valid range: Off, 3
to 24 months (in 3 month increments)
4.3 UV LAMP
This feature displays an alert to remind the user to change
the UV lamps after the selected time has passed.
Adjust the UV Lamp Reminder settings using the up/down
arrow buttons. Press the center button to save changes.
Cumulative Run Time (default Off) – valid range:
Off, 400 to 3600 hours (in 100 hour increments)
Calendar Time (default Off) – valid range: Off, 3
to 48 months (in 3 month increments)
4.4 AIR CLEANER
This feature displays an alert to remind the user to clean the
lter(s) after the selected time has passed.
Adjust the Air Cleaner Reminder settings using the up/down
arrow buttons. Press the center button to save changes.
Cumulative Run Time (default Off) – valid range:
Off, 400 to 3600 hours (in 100 hour increments)
Calendar Time (default Off) – valid range: Off, 3
to 24 months (in 3 month increments)
6.0 Humidity Con guration
Con gure humidity control settings (dehumidi cation/
humidi cation).
Adjust the Humidity Control settings using the up/down arrow
buttons. Press the center button to save changes.
• Dehumidi cation – This logic will communicate
a Dehumidi cation output when the humidity is
greater than the setpoint (acts as a dehumidistat).
The Dehumidi cation output will not be
communicated when the humidity is below the
setpoint.
• Humidi cation – This logic will communicate a
Humidi cation output when the humidity is less
than the setpoint (acts as a humidistat). When the
Humidi cation output is active, the fan output will
also be active. The Humidi cation output will not
be communicated when the humidity is above the
setpoint.
• Both – Incorporates both Dehumidi cation and
Humidi cation logic.
• None (default) – Dehumidi cation
and Humidi cation outputs will not be
communicated.
7.0 Temperature Algorithm
Con gure the logic the thermostat uses to meet the
temperature setpoints.
Proportional Integral (default) – This logic will
use a combination of temperature differential and
operating time to determine the appropriate heating
or cooling stages for operation (see NOTE 1).
Proportional Integral (No Down Staging) – This
logic includes the Proportional Integral logic, but
in addition the logic keeps all active heating or
cooling stages energized until the demand is fully
satis ed (see NOTE 1).
• Differential – This logic will only use temperature
differential to determine the appropriate heating or