Heat & Glo • Everest • 750-900 Rev. o • 10/08 10
3
Installing the Fireplace
Step 1. Locating the Fireplace
The diagram below shows space and clearance require-
ments for locating a replace within a room.
A B C D E
35 1/2” 21 3/4” 30 1/2” 43 1/4” 61 3/16”
(902 mm) (552 mm) (775 mm) (1099 mm) (1554 mm)
Minimum Clearances
from the Fireplace to Combustible Materials
Inches mm
Glass Front .........................36 ..............914
Floor .............................0 ..................0
Rear ........................... 1/2 ................13
Sides ........................... 1/2 ................13
Top ..........................4 1/2 .............114
Ceiling* ............................31 ...............787
Figure 2. Fireplace Dimensions, Locations, and
Space Requirements
Framing should be
constructed of 2 X 4
lumber or heavier.
A. ..... 35-1/8” (892 mm)
B. ..... 50-1/2” (1283 mm)
C. ..... 21-3/8” (542 mm)
D. ..... 55-1/2” (1372 mm)
Figure 3. Framing Dimensions
For minimum clearances, see the direct vent termination
clearance diagrams on pages 20 and 21 in this manual.
Minimum Clearances
from the Vent Pipe to Combustible Materials
Inches mm
Vertical Sections. ..............1 ................25
Horizontal Sections
Top ......................................3 .................75
Bottom ................................1 .................25
Sides...................................1 .................25
At Wall Firestops
Top ......................................3 .................76
Bottom ................................1 .................25
Sides...................................1 .................25
A
B
4” (102 mm)
D
C
E
1/2” (13 mm)
Shows center of
10” x 12” vent framing
holes for venting.
C
B
A
D
* The clearance to the ceiling is measured from the
top of the unit, excluding the stand-offs and collar.
See Figure 24 for further details.
(Center of 12 x 10)
Clearance Requirements
The top, back, and sides of the replace are de ned by
stand-offs. The minimum clearance to a perpendicular wall
extending past the face of the replace is 4 inches (102
mm). The back of the replace may be recessed 23 (584
mm) inches (546 mm) into combustible construction.
Step 2. Framing the Fireplace
Fireplace framing can be built before or after the replace is
set in place. Framing should be positioned to accommodate
wall coverings and replace facing material. The diagram
below shows framing reference dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS, AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS, BEFORE FRAMING.
The distance from the unit to combustible construction is
to be measured from the unit outer wrap surface to the
combustible construction, NOT from the screw heads
that secure the unit together.