Hearth and Home Technologies Cyclone-Cust Indoor Fireplace User Manual


 
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 17
A. Pipe Clearances to Combustibles
6
6
Vent Clearances and Framing
B. Wall Penetration Framing
Combustible Wall Penetration
Frame a hole in a combustible wall for an interior wall
shield restop, (Figure 6.2) whenever a wall is penetrated.
Use same size framing materials as those used in the wall
construction. The wall shield restop maintains minimum
clearances and prevents cold air in ltration.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one
inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield restop is only required on one side and no heat
shield is necessary.
If your local inspector requires the wall shield restop on
both sides, then both wall shield restops must have a heat
shield attached to them.
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as
speci ed.
• Do not pack air space with insulation or
other materials.
Failure to keep insulation or other materials
away from vent pipe may cause re.
Figure 6.1 Pipe Clearances
1 in. CLEARANCE
AROUND VERTICAL
SECTIONS
3 in. TOP
CLEARANCE
1 in. SIDE AND
BOTTOM CLEARANCE
Figure 6.2 Exterior Wall Hole
Note: Slope
not required.
10 in. X 10 in.
FRAMED
OPENING
FINISHING
MATERIAL
DECORATIVE
FIRESTOP
41-3/8 in.
(+0 to -1/2 in.)
WARNING