Hearth and Home Technologies CUMBGAP-PMH Indoor Fireplace User Manual


 
R
Page 6
September 1, 2008
Cumberland Gap Wood Stove
7006-188E
B
A
C1
Non-fuel
door side
D2
Fuel Door
side
C2
D1
CLEARANCES TO COMBUSTIBLES (UL and ULC)
G (Ceiling)
H
E1
E2
F1
F2
Fuel door
side
Non-fuel
door side
G
(Ceiling)
Max Mantel Dept
h
10" (254mm)
G
(Mantel)
IF SIDE FUEL LOADING DOOR IS NOT USED:
• Must remain in the locked position at all times
• Use clearances for non-fuel side door for both sides
TOP VENT VERTICAL
A B C1 C2 D1 D2 E1 E2 F1 F2 G H
Single Wall-USA 13(330) 11.5(292) 27(686) 27(686) 18(457) 18(457) 16.5(419) 16.5(419) 20(508) 20(508) 56.5(1435) N/A
Single Wall-Canada 13(330) 11.5(292) 27(686) 27(686) 18(457) 18(457) 16.5(419) 18(457) 20(508) 21.5(546) 56.5(1435) N/A
Double Wall-USA 12(305) 10.5(267) 25(635) 26(660) 15(381) 16(406) 11(279) 16(406) 14(356) 19(483) 56.5(1435) N/A
Double Wall-Canada 12(305) 10.5(267) 25(635) 28(711) 15(381) 18(457) 11(279) 18(457) 14(356) 21(533) 56.5(1435) N/A
HORIZONTAL WITH MINIMUM 2FT (609mm) VERTICAL OFF STOVE TOP. (Note: Horizontal must be with 2ft (609mm) vertical
and NOT directy off stove).
Single Wall-USA 13.5(343) 12(305) 27(686) 27(686) 17(432) 17(432) N/A N/A N/A N/A 42.5(1080) 10.5(267)
Single Wall-Canada 13.5(343) 12(305) 27(686) 28(711) 17(432) 18(457) N/A N/A N/A N/A 42.5(1080) 10.5(267)
Double Wall-USA 11(279) 9.5(241) 27(686) 27(686) 17(432) 17(432) N/A N/A N/A N/A 39(991) 8(203)
Double Wall-Canada 11(279) 9.5(241) 27(686) 28(711) 17(432) 18(457) N/A N/A N/A N/A 39(991) 8(203)
ALCOVE -
Six inch (6") (152mm) diameter listed DOUBLE WALL air insulated connector pipe with UL103 HT listed factory-built Class "A"
chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor.)
Double Wall-USA 12(305) 10.5(267) 25(635) 26(660) 15(381) 16(406) N/A N/A N/A N/A 44(1118) N/A
Double Wall-Canada 12(305) 10.5(267) 25(635) 28(711) 15(381) 18(457) N/A N/A N/A N/A 44(1118) N/A
REAR VENT INSTALLATIONS
IN A MASONRY FIREPLACE OR THROUGH THE WALL .
HORIZONTAL FLUE HEAT SHIELD, PART HTSHLD-7006,
REQUIRED ON REAR VENT INSTALLATIONS:
Six inch (6") (152mm) diameter listed double wall air insulated connector pipe with UL103 HT listed
factory-built Class "A" chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor). Additional specifications include a
MAXIMUM 10" (254mm) MANTEL WIDTH and the following clearances.
Double Wall-USA N/A 12(305) 27(686) 27(686) 17.5(445) 17.5(445) N/A N/A N/A N/A 39(991) ceiling N/A
Double Wall-Canada N/A 12(305) 27(686) 27.5(699) 17.5(445) 18(457) N/A N/A N/A N/A 39(991) ceiling N/A
USA or Canada - Single or Double Wall Pipe: 31(787) mantel N/A
USA or Canada - Single or Double Wall Pipe: 24(610) mantel
*
N/A
*with metal shield spaced 1" (25mm) away from bottom mantel surface
HEARTH MOUNT - SIDE DOOR MUST BE LOCKED CLOSED
Single Wall-USA 18(457) 10(254) 22(559) 31(787) N/A N/A N/A N/A N/A N/A N/A N/A
Single Wall-Canada 18(457) 10(254) 22(559) 31(787) N/A N/A N/A N/A N/A N/A N/A N/A
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS: In Inches & (Millimeters)
NOTE: All "A" , "C" and "F" Dimensions are to the inside diameter of the flue collar.
Max Depth Min Width Min Height
Front Door 48(1219) 55(1397) 72(1829)
Side Door-USA 48(1219) 57(1448) 72(1829)
Side Door-Canada 48(1219) 61(1549) 72(1829)
NOTE: Optional Fire Screen, Part SCR-7006, can only be used in FULL Vertical installations