5100-I WOOD INSERT
R
250-1960 Rev B
FACTORY BUILT ZERO CLEARANCE FIREPLACE
(USA INSTALLATONS ONLY)
The Quadra-Fire 5100-I Insert is listed to UL Standards for Safety 127 and approved for installation and use in factory built
zero clearance replaces conforming to the following specications:
The following modications of factory built replaces are permissible: 1) removal of damper; 2) removal of smoke shelf
or bafe; 3) removal of ember catches; 4) removal of re grate; 5) removal of viewing screen/curtain; and, 6) removal of
doors.
NOTE: Installation into replaces without a permit will void the listing.
The factory built chimney must be listed per UL 127 and meet the type HT requirements of UL 103. Factory built replace
chimneys tested to UL 127-1998, may be at the replace manufacturer’s option, tested to the same criteria as UL 103 HT
requirements. If the chimney is not listed as meeting HT requirements, or if the factory built replace was tested prior to
1998, a full height listed chimney liner must be installed from the appliance ue collar to the chimney top. The liner must
meet type HT requirements (2100ºF) per UL 1777. The liner must be securely attached to the insert ue collar and the
chimney top. To prevent room air passage to the chimney cavity of the replace, seal either the damper area around the
chimney liner with high temperature sealant or the replace front with berglass batting.
The replace must not be altered, except that the damper may be removed to accommodate a direct-connect starter pipe
or chimney liner, and external trim pieces which do not affect the operation of the replace may be removed providing
they can be stored on or within the replace for reassembly if the insert is removed. The permanent metal warning label
provided must be attached to the back of the replace, with screws or nails, stating that the replace may have been
altered to accommodate the insert, and must be returned to
original condition for use as a conventional replace.
If the hearth extension is lower than the replace opening,
the portion of the insert extending onto the hearth must be
supported. Manufacturer designed adjustable support kit
can be ordered from your dealer. (See page 16).
Final approval of this installation type is contingent upon
the authority having jurisdiction.
Listed Liner
Mantel
SEAL DAMPER AREA OR FACE SEAL
Figure 11A - Installation Into A Factory Built
Zero Clearance Fireplace
36”
24”
19”
915mm
610mm
483mm
Minimum Width of cavity opening:
Minimum Height:
Minimum Depth from front to rear: