Hearth and Home Technologies 4100I-NL-B Indoor Fireplace User Manual


 
Page 5
September 1, 2008
4100-I ACT WOOD INSERT
250-7201E
R
Hearth Extension
A
B
C
D
F
E
Insert
SideWall
Maximum Mantel Depth - 10" (254mm)
Fascia or Trim
Mantel
Thermal Protection USA & Canada
USA CANADA
A Sidewall to Stove 15" (381mm) 15" (381mm)
B Mantel to Stove 26" (660mm) 23" (584mm)
C Top Trim to Stove 20" (508mm) 20" (508mm)
D Side Trim to Stove 6" (152mm) 6" (152mm)
E Hearth Extension from Glass 16" (406mm) 18" (457mm)
F
Hearth Extension from Side of Insert
8" (203mm) 8" (203mm)
Thermal protection must be 1/2 Inch (12.7mm) minimum
thickness ('k" value = 0.84) or equivalent material*
*Zero Clearance Installations USA Only
Omni Report #061-S-40-2
In Canada a full length six inch (152mm) S65 ue liner
required as per ULC S628.
CLEARANCES TO COMBUSTIBLES
United States and Canada
*
NOTE: When installing into a masonry replace, the re-
place must be built to UBC Chapter 7 standards. Do not
remove brick or mortar from masonry replace to accom-
modate insert. The permanent metal warning plate provided
must be attached to the back of the replace stating the re-
place may have been altered to accommodate the insert and
must be returned to original condition for use as a conven-
tional replace.