Hearth and Home Technologies 4100I-NL-B Indoor Fireplace User Manual


 
4100-I ACT WOOD INSERT
Page 10
September 1, 2008
R
250-7201E
MASONRY FIREPLACE
USING DIRECT-CONNECT METHOD



Direct Connect
Seal Option
Minimum Starter
Pipe Option
Full Listed
Liner Option
Masonry Chimney
Flue Tile
Mantel
Air-tight Face Seal
Damper Area
SEAL DAMPER AREA OR FACE SEAL
INSTALLATION OPTIONS
This product conforms with the UL Standard for Safety
1482 (USA) and ULC S628 (Canada) in all respects, and
is approved to UL & ULC safety standards for installation
and use within a replace with a masonry chimney in accor-
dance with NFPA 211, with or without a direct ue collar con-
nection. A starter pipe is required to reach to the bottom of
the existing ue.
1. Secure the replace damper in the open position. If this
cannot be accomplished, it will be necessary to remove
the damper.
2. Seal either the damper area around the chimney liner
with a high temperature sealant or the replace front with
berglass batting.
. The chimney should be examined for cracks, loose
mortar, and other signs of deterioration and blockage.
The insert should not be installed until it is determined
that the chimney is safe for use. Since an oversized ue
contributes to the accumulation of creosote, the size of
the ue should be checked to determine that it is not too
large for the insert. The chimney should also be checked
to ensure it meets the minimum standard of the National
Fire Protection Association (NFPA) Standard 211. The
following bullets list the more critical requirements for a
properly constructed chimney:
The masonry wall of the chimney, if brick or modular
block, must be a minimum of 4 inches (102mm) nominal
thickness. A chimney of rubble stone must be at least 12
inches (05mm) thick
The chimney must have a re clay ue liner (or equiva-
lent) with a minimum thickness of 5/8” (16mm) and must
be installed with refractory mortar. An equivalent liner
must be a listed chimney liner system or other approved
material.
Cross-sectional area should be no more than  times the
cross-sectional area of the ue collar of the insert. (28 sq
inch ue area x  inches = 84 square inches maximum
chimney area).
A chimney inside the house must have at least two inches
(51mm) of clearance to the combustible structure. A chim-
ney outside the house must have at least 1 inch (25mm)
clearance to the combustible structure. Non-combustible
re stops must be installed at the spaces where the chim-
ney passes through oors and/or ceiling 
.
NOTE: In Canada, a full reline is required.
METAL HEAT CIRCULATING MASONRY
This product conforms with the safety standard UL1482
(USA) and ULC S628 (Canada) in all respects and is
approved to UL & ULC safety standards for installation and
use within a replace with masonry chimney, in accordance
with NFPA 211, with or without a direct ue collar connec-
tion. A starter pipe is required into existing chimney.
- 

Listed Liner
Mantel
SEAL DAMPER AREA OR FACE SEAL