Goodman Mfg GMV95/GCV9 Furnace User Manual


 
6 www.goodmanmfg.com SS-GMV95
PRODUCT SPECIFICATIONS
GMV95 HIGH- OR SINGLE-STAGE COOLING SPEEDS
GMV95 LOW-STAGE COOLING SPEEDS
GMV950453BXB GMV950704CXB GMV950905DXB GMV951155DXB
Cooling
Speed Tap
Adjust
Tap
CFM¹
Cooling
Speed Tap
Adjust
Tap
CFM¹
Cooling
Speed Tap
Adjust
Tap
CFM¹
Cooling
Speed Tap
Adjust
Tap
CFM¹
A
Minus (-) 540
A
Minus (-) 540
A
Minus (-) 720
A
Minus (-) 720
Normal 600 Normal 600 Normal 800 Normal 800
Plus (+) 660 Plus (+) 660 Plus (+) 880 Plus (+) 880
B
Minus (-) 720
B
Minus (-) 720
B
Minus (-) 990
B
Minus (-) 990
Normal 800 Normal 800 Normal 1,100 Normal 1,100
Plus (+) 880 Plus (+) 880 Plus (+) 1,210 Plus (+) 1,210
C
Minus (-) 900
C
Minus (-) 990
C
Minus (-) 1,260
C
Minus (-) 1,260
Normal 1,000 Normal 1,100 Normal 1,400 Normal 1,400
Plus (+) 1,100 Plus (+) 1,210 Plus (+) 1,540 Plus (+) 1,540
D
Minus (-) 1,080
D
Minus (-) 1,286
D
Minus (-) 1,620
D
Minus (-) 1,620
Normal 1,200 Normal 1,429 Normal 1,800 Normal 1,800
Plus (+) 1,320 Plus (+) 1,572 Plus (+) 1,980 Plus (+) 1,980
¹ @ .1” to .8” W.C. ESP
Notes:
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
Do not operate above .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only.
Constant Fan mode is 50% of above values
GMV950453BXB GMV950704CXB GMV950905DXB GMV951155DXB
Cooling
Speed Tap
Adjust
Tap
CFM¹
Cooling
Speed Tap
Adjust
Tap
CFM¹
Cooling
Speed Tap
Adjust
Tap
CFM¹
Cooling
Speed
Tap
Adjust
Tap
CFM¹
A
Minus (-) 380*
A
Minus (-) 378*
A
Minus (-) 513*
A
Minus (-) 514*
Normal 390 Normal 390 Normal 520 Normal 520
Plus (+) 429 Plus (+) 429 Plus (+) 572 Plus (+) 572
B
Minus (-) 468
B
Minus (-) 468
B
Minus (-) 644
B
Minus (-) 644
Normal 520 Normal 520 Normal 715 Normal 715
Plus (+) 572 Plus (+) 572 Plus (+) 787 Plus (+) 787
C
Minus (-) 585
C
Minus (-) 644
C
Minus (-) 819
C
Minus (-) 819
Normal 650 Normal 715 Normal 910 Normal 910
Plus (+) 715 Plus (+) 787 Plus (+) 1,001 Plus (+) 1,001
D
Minus (-) 702
D
Minus (-) 836
D
Minus (-) 1,053
D
Minus (-) 1,053
Normal 780 Normal 929 Normal 1,170 Normal 1,170
Plus (+) 858 Plus (+) 1,022 Plus (+) 1,287 Plus (+) 1,287
¹ @ .1” to .8” W.C. ESP
Notes:
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
Do not operate above .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only.