GE AE0CD20DM Air Conditioner User Manual


 
15
Installation Instructions
INSTALL THE OUTDOOR UNIT
• Install the connection tube
1. Align the center of the tubing flare with the
relevant valve.
2. Screw in the flare nut by hand and then tighten
the nut with spanner and torque wrench. See
the table below for the correct torque.
3. Connecting tube specifications are shown
below:
NOTE: Exceeding tightening torque will damage
the copper tubing.
NOTE: To prevent wind and pest infiltration,
seal holes around the tubing and wiring with
the supplied sealer.
10
PURGE THE AIR AND
TEST FOR LEAKAGE
1. Install the connecting tubes of the
indoor/outdoor unit.
2. DO NOT OPEN THE GAS VALVES UNTIL THE
EVACUATION PROCESS IS COMPLETE.
3. Remove the gas line service port cap and
connect the gas valves of the vacuum gauge,
vacuum pump and outdoor unit.
NOTE: Connect by using a 1/4Female x
1/2Male Adapter Access Fitting (obtain locally).
4. Start the vacuum pump. (Running time should
be more than 15 minutes.)
5. Check the vacuum with the vacuum gauge. The
gauge should read -30 in. Hg. After evacuation,
fully close the handle on the manifold valve
(on the vacuum pump device). Then stop the
vacuum pump and disconnect it.
6. The pressure should be kept for 1–2 minutes
to confirm that the reading of the vacuum
gauge does not change. The pressure should
be -30 in. Hg.
7. Remove the vacuum line and replace the service
port cap.
8. Remove both the liquid and gas valve caps.
9. Open the gas and liquid valve entirely, using
the 5 mm Allen wrench. If this is not done, the
performance will be reduced, or an error will
occur.
10. Replace the caps and tighten securely.
11
Cap
Liquid tube
Gas tube
Vacuum pump
Vacuum gauge
INSTALLATION (cont.)
2
Tubing OD Tightening torque (in./lb.)
1/4 140–170
3/8 270–310
1/2 440–480
5/8 530–570
Tightening torque table
Torque wrench
Flare nut
Joint
Spanner
10,000/14,000 20,000
Specifications BTU Units BTU Units
Design Length 20 ft. 26.2 ft.
Extra Refrigerant Charge 0.16 oz./ft. 0.54 oz./ft.
Per Ft. Above Design Length
Outer Diameter Liquid Pipe 1/4 3/8
Outer Diameter Gas Pipe 1/2 5/8
Max. Distance Height 33 ft. 33 ft.
Max. Distance Length 68 ft. 98 ft.