Stovax Open Log Burning Convector Fireboxes Indoor Fireplace User Manual


 
PRE-INSTALLATION CHECKS
Model
Flue/Chimney Size
Without liner system (round)
minimum dimension (diameter.)
mm 200 200 200 200 200
inch 8 8 8 8 8
Without liner system (square)
minimum dimension
mm 185 185 185 185 185
inch 7 1/4 7 1/4 7 1/4 7 1/4 7 1/4
Liner or factory made system
(diameter.)
installed in accordance with manufacturers instructions
mm 200 200 200 200 200
inch 8 8 8 8 8
Do not connect to systems containing large voids or over 9" (230mm) square/round
Flue/Chimney
minimum height*
All Products
m 4.5 4.5 4.5 4.5 4.5
feet 15 15 15 15 15
* When measured from the top of the appliance to the top of the flue, with no horizontal sections
and a maximum of 4 bends with angles of less than 45°
16" Riva
Open
22" Riva
Open
24" Riva
Open
26" Riva
Open
28" Riva
Open
17
1.1 This appliance requires ventilation to supply combustion air.
Any room containing the appliance must have a permanent
air vent opening with a total free area of at least 550mm
2
per kW of appliance rated output above 5kW.
1.2 Increase air supply provisions where a room contains
multiple appliances.
1.3 If vents open into adjoining rooms or spaces there must be
an air vent of at least the same size direct to the outside.
1.4 Permanent air vents should be non-adjustable and
positioned where they are unlikely to become blocked.
1.5 Site the vents where cold draught is unlikely to cause
discomfort. This can be avoided by placing vents near
ceilings or close to the appliance, see Diagram opposite.
1. VENTILATION