Kühl E-Control Service Kit
1 fo 1 egaP .oC gninoitidnoC riA hcirdeirF )21/7( 00_65891029
10001 Reunion Place, Suite 500 / San Antonio, Texas 78216
(210) 546-0500 / (800) 541-6645 / www.friedrich.com
Configuration Instructions – Electronic Control Gen. 2
For Use with Kühl (cool only models) and Kühl + (cool and heat models) N models.
Example SS08N
10-A
Notice: Please read these instructions completely before attempting configuration.
WARNING: Refer to the table below to determine the appropriate Electronic Control Kit part number by unit model
number prefix. Failure to install the correct Electronic Control Kit for the given unit model may result in failure of the
product and/or a potentially unsafe operating condition.
FRIEDRICH ELECTRONIC CONTROL KIT PART # FRIEDRICH MODEL PREFIX
MS ,SS 01010626
LS 11010626
)woleb ees ,01SY edulcni ton seod*( LY ,MY ,*SY 21010626
LE ,ME ,SE 31010626
01N01SY 41010626
Contents:
Main Board
Indoor Air Sensor
Indoor Coil Sensor
Outdoor Coil Sensor
Discharge Air Sensor
Instruction Sheet
Procedure
:
You must first confirm and set the voltage of the electronic control to match
your air conditioner.
Please perform the steps listed below before installation:
Step 1. Identify unit operating voltage from unit nameplate label.
Step 2. Set voltage selection on the electronic control by connecting the
jumper wire(s) to match the voltage listed on the unit nameplate label.
Step 3. Consult service manual for electronic control replacement
instructions and safety information.
115V Configuration
230V Configuration