VENTING INSTALLATION
Continued
Figure 9 - Elbow Offset
B
A
Screws
FIRESTOP SPACERS (FS-8DM)
Firestopspacersarerequiredateachpoint
wherethechimneypenetratesaoorspace.
Theirpurposeistoestablishandmaintain
the required clearance between the chimney
andthecombustiblematerials.Whenthepipe
passes through a framed opening into a living
spaceabove,therestopmustbeplacedonto
theceilingfrombelowasshowninFigure10.
Theyalsoprovidecompleteseparationfrom
oneoorspacetoanotheroratticspaceas
requiredbymostcodes.Whenthedoublewall
pipe passes through a framed opening into an
atticspace,therestopmustbeplacedintoan
atticoorasshowninFigure11.
Figure 10 - Firestop Spacer with Living
Space Above Ceiling
Figure 11 - Firestop Spacer with Attic
Space Above Ceiling
Existing
Ceiling
Frame
Firestop
Spacer
Screwsor
Staples
(Min.of8)
Firestop
Spacer
ScrewsorStaples
(Min.of8)
PENETRATING ROOF
Tomaintaina1"clearancetothepipeona
roof with a pitch, a rectangular opening must
be cut.
1. Determinethecenterpointthroughwhich
the pipe will penetrate the roof.
2. Determinethecenterpointoftheroof.
Pitchisthedistancetheroofdropsover
a given span, usually 12". A 6/12 pitch
means that the roof drops 6" for each 12"
onemeasurehorizontallydownfromthe
roof rafters.
3. Usetheroofopeningchart(Figure12,
page 9) to determine the correct opening
lengthandashingrequired.
4. Removetheshinglesaroundtheopening
measured.Cutoutthissection.
5. Add the next sections of the pipe until the
endpenetratestheroofline.Checktosee
that the proper clearances are maintained.
Extend chimney by adding sections of
double wall pipe until pipe is minimum of
30" above the highest point of the roof cut-
out.Terminationandchimneymustextend
a minimum of 36" above the highest point
where it passes through the roof.
Existing
Ceiling
Frame
Figure 8 - Ceiling Support Pipe
12S-8DM
2"Min.
Straps
Straps
Straps
Straps
DetailA
ReturnElbow
DetailB
AngleFirestop
SeeDetailA
SeeDetailB