Energy Tech Laboratories MR212 Gas Heater User Manual


 
26
Burner Orifice
Drill Size
Orifice Drill Size
Gas Port 31
Air Port 43
2 weeks after startup
1. Belt tension should be checked after the first 2 weeks of fan operation. Belts tend to stretch and
settle into pulleys after an initial start-up sequence. Do not tension belts by changing the
setting of the motor pulley, this will change the fan speed and may damage the motor. To re-
tension belts, turn the power to the fan motor OFF. Loosen the fasteners that hold the blower
scroll plate to the blower. Rotate the motor to the left or right to adjust the belt tension. Belt
tension should be adjusted to allow 1/64” of deflection per inch of belt span. Exercise extreme
care when adjusting V-belts as not to misalign pulleys. Any misalignment will cause a sharp
reduction in belt life and produce squeaky noises. Over-tightening will cause excessive belt and
bearing wear as well as noise. Too little tension will cause slippage at startup and uneven wear.
Whenever belts are removed or installed, never force belts over pulleys without loosening
motor first to relieve belt tension. When replacing belts, use the same type as supplied by the
manufacturer. On units shipped with double groove pulleys, matched belts should always be
used.
2. All fasteners should be checked for tightness each time maintenance checks are preformed prior
to restarting unit.
Every 3 months
1. Belt tension should be checked quarterly. See instructions in the previous maintenance section.
Over-tightening will cause excessive bearing wear and noise. Too little tension will cause
slippage at startup and uneven wear.
2. Filters need to be cleaned and/or replaced quarterly, and more often in severe conditions.
Washable filters can be washed in warm soapy water. When re-installing filters, be sure to install
with the airflow in the correct direction as indicated on the filter.
Filter Quantity Chart
Intake 16” x 20” 20” x 25”
Size 1 Sloped 3
Size 2 Sloped 3
Size 3 Sloped 6
Size 4 Sloped 10
Size 5 Sloped 8
Size 1 V-Bank 3
Size 2 V-Bank 8
Size 3 V-Bank 8
Size 4 V-Bank 15
Size 5 V-Bank 12
Yearly
1. Inspect bearings for wear and deterioration. Replace if necessary.
2. Inspect belt wear and replace torn or worn belts.
3. Inspect bolts and set screws for tightness. Tighten as necessary.
4. Inspect motor for cleanliness. Clean exterior surfaces only. Remove dust and
grease from the motor housing to ensure proper motor cooling. Remove dirt
and grease from the wheel and housing to prevent imbalance and damage.
5. Check for gas leaks and repair if present.
6. Clean flame sensor by rubbing with steel wool to remove any rust build-up,
7. Clean burner with a wire brush and insure burner ports are free of debris.
Then wipe the burner with a clean rag.