Envision Peripherals Geothermal Indoor Split Heat Pumps Heat Pump User Manual


 
9
ENVISION SERIES INSTALLATION MANUAL
Air Handler Coil Data
Notes: * Variable speed air handler required for all dual capacity units.
Line Set Sizes
Envision
Split Model
Matching Air
Handler
Coil Surface
Area (sq ft.)
FPI Rows
Tube
Diameter
022 - 038
042 - 072
NAH060 5.83 12 3 3/8"
NAH036 5.83 12 2 3/8"
Unit Air Factory
Size Handler
Suction Liquid Suction Liquid Suction Liquid
Charge (oz.)
NZ022 NAH036 5/8" OD 3/8" OD 5/8" OD 3/8" OD 3/4" OD 3/8" OD 56
NZ030 NAH036 5/8" OD 3/8" OD 3/4" OD 3/8" OD 3/4" OD 3/8" OD 56
NZ036 NAH036 5/8" OD 3/8" OD 3/4" OD 3/8" OD 3/4" OD 1/2" OD 56
NZ042 NAH060 3/4" OD 3/8" OD 3/4" OD 3/8" OD 7/8" OD 1/2" OD 74
NZ048 NAH060 3/4" OD 3/8" OD 7/8" OD 3/8" OD 7/8" OD 1/2" OD 90
NZ060 NAH060 7/8" OD 1/2" OD 7/8" OD 1/2" OD 1-1/8" OD 1/2" OD 92
NZ070 NAH060 7/8" OD 1/2" OD 7/8" OD 1/2" OD 1-1/8" OD 1/2" OD 108
NZ026 NAH036 5/8" OD 3/8" OD 3/4" OD 3/8" OD 3/4" OD 1/2" OD 52
NZ038 NAH036 5/8" OD 3/8" OD 3/4" OD 3/8" OD 3/4" OD 1/2" OD 56
NZ049 NAH060 3/4" OD 3/8" OD 7/8" OD 3/8" OD 7/8" OD 1/2" OD 90
NZ064 NAH060 7/8" OD 1/2" OD 7/8" OD 1/2" OD 1-1/8" OD 1/2" OD 92
NZ072 NAH060 7/8" OD 1/2" OD 7/8" OD 1/2" OD 1-1/8" OD 1/2" OD 104
Notes: Lineset charge for R410A is 0.50 oz. per ft. for 3/8" and 1.0 oz. per ft. for 1/2" tube.
Rev.: 6/8/07
Initial Total System Charge = Factory Envision Split charge + lineset charge + 20 oz, then adjust charge by subcooling and superheat measurements.
20 feet 40 feet 60 feet