Envision Peripherals Geothermal Indoor Split Heat Pumps Heat Pump User Manual


 
26
ENVISION SERIES INSTALLATION MANUAL
Single Speed Models
Unit Operating Parameters
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Water Temp
Rise °F
Air Temp
Drop °F DB
1.5 120 - 142 215 - 240 7 - 15 7 - 14 18 - 22 18 - 22
3.0 115 - 138 190 - 225 10 - 18 4 - 11 8 - 10 18 - 22
1.5 125 - 148 290 - 315 8 - 14 6 -11 18 - 22 18 - 22
3.0 123 - 146 255 - 290 9 - 15 5 - 10 8 - 10 18 - 22
1.5 134 - 157 340 - 380 8 - 14 6 - 13 18 - 22 16 - 20
3.0 130 - 155 310 - 350 9 - 15 5 - 12 8 - 10 16 - 20
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Water Temp
Drop °F
Air Temp
Rise °F DB
1.5 69 - 81 254 - 334 7 - 13 5 - 13 7 -10 18 - 24
3.0 75 - 87 260 - 340 7 - 14 5 - 13 3 - 6 20 - 26
1.5 98 - 113 293 - 373 7 - 14 7 - 15 8 - 11 20 - 26
3.0 105 - 120 300 - 380 7 - 15 7 - 15 4 - 7 22 - 28
1.5 133 - 150 315 - 415 9 - 15 9 - 16 11 - 14 26 - 32
3.0 139 - 157 325 - 425 9 - 15 9 - 16 7 - 10 28 - 34
Entering Water
Temp °F
Water Flow
GPM/Ton
Cooling -- No Desuperheater
50
70
90
Entering Water
Temp °F
Water Flow
GPM/Ton
Heating -- No Desuperheater
30
50
70
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.