29
ENVISION SERIES INSTALLATION MANUAL
15. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps
deactivate.
16. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
17. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
18. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
Notes: Be certain to ll out and forward all warranty registration papers.
Final Evaluation
After the initial check of superheat/subcooling values in the heating mode, shut off the unit and allow it to sit 3 to 5 min-
utes until pressures equalize. Restart the unit in the cooling mode and check the values against those in tables on pages 26
and 27. If the unit performs satisfactorily, charging is complete. If the unit does not perform to specications, the charge may
need to be readjusted until the values are close. Adding refrigerant will increase subcooling. Recovering some of the refrig-
erant will decrease subcooling and increase superheat. If the superheat/subcooling values are still not close to the specica-
tions in tables on pages 26 and 27, analyze refrigerant circuit operation.