Enviro EF4 Stove User Manual


 
Installation
CLEARANCES TO COMBUSTIBLES - FREESTANDING:
When installing this unit on a combustible floor (eg. wood linoleum) a non-combustible hearth pad must
be under the unit. The pad must extend at least the width of the appliance [22” (558 mm)] and at least
the depth of the appliance plus 6” (150 mm) in front of the appliance [27 ” (699 mm)].
Side wall to unit - 6 inches (15 cm)
Back wall to unit - 2 inches (5 cm)
Corner to unit - 2 inches (5 cm)
Door front to edge of floor protection
- 6 inches (15 cm)
48"
(122 cm)
48"
(122 cm)
36"
(91cm)

 

 

 

 
 
 


 
Figure 8: EF4 Freestanding Clearance to Combustibles.
Minimum Alcove width - 36 inches (91 cm)
Minimum Alcove height - 48 inches (122 cm)
Maximum Alcove depth - 48 inches (122 cm)
Figure 9: EF4 Freestanding Minimum Alcove Size.
CLEARANCES TO COMBUSTIBLES - FIREPLACE INSERT:
Side wall to unit - 9 inches (22.9 cm)
Mantel projection - 10 inches (25.4 cm)
Mantel to top of unit - 8 inches (20.3 cm)
Facing on masonry fireplace edge
- 9 inches (22.9 cm)
Minimum solid fuel burning fireplace opening:
Height - 21” (53.7 cm)
Width - 22” (58.9 cm)
Depth - 21” (54.6 cm)
10" (25.4 cm) Mantel
9"
(22.9 cm)
8"
(20.3 cm)
Side Wall
Figure 10: EF4 Fireplace Insert Clearance to Combustibles.
13
These dimensions are minimum clearances but it is
recommended that you ensure sufficient room for
servicing, routine cleaning and maintenance.