become hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.
3. Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe
be installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent
the possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing
a nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred
venting method is to extend the vent through the roof vertically.
4. Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the
plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located in
the vicinity of termination. The grade surface must not be lawn.
5. If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior
of the house might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no
guarantee against such incidents.
6. When installing an FPI the chimney must be fully lined. Unless the chimney’s inside diameter is less than 6”
(15 cm) around or has a cross section area of 28 inches² (180.6 cm²), we strongly recommend lining all masonry
chimneys.
NOTE: Venting terminals shall not be recessed into walls or siding.
Installation
VENT TERMINATION REQUIREMENTS:
IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER.
Figure 15: Use in conjunction with Table 1 for allowable exterior vent termination locations.
Table 1: Use in conjunction with Figure 15 for allowable exterior vent termination locations.
Letter Minimum Clearance Description
A 24 in (61 cm) Above grass, top of plants, wood, or any other combustible materials.
B 48 in (122 cm) From beside/below any door or window that may be opened.
C 24 in (61 cm) From above any door or window that may be opened.
D 24 in (61 cm) To any adjacent building, fences and protruding parts of the structure.
E 24 in (61 cm) Below any eave or roof overhang
F 12 in (30 cm) To outside corner.
G 12 in (30 cm) To inside corner, combustible wall (vertical and horizontal terminations).
H 3 ft (91 cm) within a height of 15 ft (4.5
m) above the meter/regulator assembly
To each side of center line extended above natural gas or propane meter/regulator assembly or
mechanical vent.
I 3 ft (91 cm) From any forced air intake of other appliance
J 12 in (30 cm) Clearance to non-mechanical air supply inlet to building, or the combustion air inlet to any appliance.
K 24 in (61 cm) Clearance above roof line for vertical terminations.
L 7 ft (2.13 m) Clearance above paved sidewalk or paved driveway located on public property.
Air Supply Inlet
Gas Meter
Restriction Zone
(Terminationnot allowed)
Termination Cap
G
G
Opens
Opens
Opens
D
F
B
B
A
I
H
K
G
G
L
C
E
1. Do not terminate the
vent in any enclosed
or semi-enclosed areas
such as a carport,
garage, attic, crawlspace,
narrow walkway, closely
fenced area, under a
sundeck or porch, or any
location that can build
up a concentration of
fumes such as stairwells,
covered breezeway, etc.
2. Vent surfaces can
15