Desa (V)KC42P SERIES Indoor Fireplace User Manual


 
www.desatech.com
116239-01D 5
LOCAL CODES
Install and use replace with care. Follow all local
codes. In the absence to local codes, use the cur-
rent National Fuel Gas Code ANSI Z223.1/NFPA
54* (USA) or the current CSA-B149.1 Installation
Code (Canada).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
PRODUCT FEATURES
These are a few facts that can help you understand
and enjoy your direct-vent replace:
The venting system may be routed to the out-
side of your home in several ways. It may vent
through the roof (vertical) or it may vent to an
outside/exterior wall (horizontal). The vent
pipe installation is very important to allow for
proper operation. You must follow the venting
instructions very carefully for either vertical or
horizontal applications.
This replace may be installed in any room of
your house provided all local codes and these
installation instructions are followed.
This replace requires a wall switch, hand-held
remote or wall thermostat (millivolt) for opera-
tion (see Accessories, page 42).
This replace does not require electricity to
operate.
Only the blower requires electricity if installed
and if you plan to install the blower at a later
date, do not forget to wire the outlet at the bot-
tom of the replace when framing.
A piezo ignitor and ceramic electrode create
spark to ignite the pilot light. It does not require
any matches, batteries or any other sources of
ignition to light the pilot.
Each time you turn on your replace, you may
notice some amount of condensation on the in-
side of the replace glass. This is normal and will
disappear after 10-20 minutes of operation.
Your direct-vent gas replace system (replace
and venting) is a balanced and sealed gas op-
erating unit. It requires approximately 10-20
minutes of operating time before the ame
pattern stabilizes.
Fireplaces with the sufx of -HA have been
designed to operate at altitudes of 4000 feet
and above.
Figure 2 - Common Fireplace Locations
Flush with a wall
Through exterior wall
enclosed in a chase
Corner
installation
Figure 3 - Fireplace Bottom Dimensions
D
RW
FW
23
1
/4"
36
1
/4"
48"
PRE-INSTALLATION
PREPARATION

REqUIREMENTS
Determine the safest and most efcient location
for your DESA direct-vent replace. Make sure
that rafters and wall studs are not in the way of the
venting system. Choose a location where the heat
output is not affected by drafts, air conditioning
ducts, windows or doors. Figure 2 shows some
common locations. Be aware of all restrictions and
precautions before deciding the exact location for
your replace and termination cap.
When deciding the location of your replace,
follow these rules:
Do not connect this replace venting to a chim-
ney ue serving a separate solid-fuel burning
replace or appliance.
Due to high temperatures, do not locate this
replace in high trafc areas, windy or drafty
areas or near furniture or draperies.
Proper clearances must be maintained.
If your replace is to be installed directly on
carpeting, vinyl tile or any combustible mate-
rial other than wood, it must be installed on a
metal or wood panel extending the full width
and depth of the replace. See Figure 3.