www.desatech.com
116239-01D22
Figure 30 - External Regulator with Vent
Pointing Down (Propane/LP Only)
Propane/LP
Supply Tank
External
Regulator
Vent
Pointing
Down
-
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from replace (see
Figure 31).
IMPORTANT: Install main gas valve (equipment
shutoff valve) in an accessible location. The main
gas valve is for turning on or shutting off the gas
to the appliance.
Check your building codes for any special re-
quirements for locating equipment shutoff valve
to replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could result
in clogged replace valves.
FIREPLACE
INSTALLATION
Continued
We recommend that you install a sediment trap/
drip leg in supply line as shown in Figure 31. Lo-
cate sediment trap/drip leg where it is within reach
for cleaning. Install in piping system between fuel
supply and replace. Locate sediment trap/drip leg
where trapped matter is not likely to freeze. A sedi-
ment trap traps moisture and contaminants. This
keeps them from going into replace gas controls.
If sediment trap/drip leg is not installed or is in-
stalled wrong, replace may not run properly.
Figure 31 - Gas Connection
CSA Design-Certied
Equipment Shutoff Valve
with 1/8" NPT Tap*
3" Minimum
Approved
Flexible
Gas Line
Cap Pipe Tee Joint
Nipple
Sediment Trap/
Drip Leg
Natural - From
Gas Meter (5.5"
W.C. to 10.5" W.C.
Pressure)
From
External Regulator
(11" W.C. to 14"
W.C. Pressure)
* The CSA design-certied equipment shutoff
valve may be supplied with the appliance or you
can purchase it from your retailer.
SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not
provided)
1. Open lower louver door panel by gently pull-
ing forward.
2. Route exible gas line (provided by installer)
from equipment shutoff valve to replace.
Route exible gas supply line through one of
the access holes on side of replace.
3. Attach exible gas line from gas supply to
control valve (see Figure 32, page 23).
4. Check all gas connections for leaks. See
Checking Gas Connections, page 23.