Desa HDCFTN Indoor Fireplace User Manual


 
www.desatech.com
111044-01J 7

construction where:
 -
 
  

-11

2


and
 
and
     
   


 


If your home meets all of the three criteria

See Ventilation Air From Outdoors
If your home does not meet all of the three
  Determining
Fresh-Air Flow For Fireplace Location

The National Fuel Gas Code, ANSI Z223.1/NFPA
54 denes a conned space as a space whose vol-
ume is less than 50 cubic feet per 1,000 Btu per hour
(4.8 m
3
per kw) of the aggregate input rating of all
appliances installed in that space and an unconned
space as a space whose volume is not less than 50
cubic feet per 1,000 Btu per hour (4.8 m
3
per kw) of
the aggregate input rating of all appliances installed
in that space. Rooms communicating directly with
the space in which the appliances are installed*,
through openings not furnished with doors, are
considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
DETERMINING FRESH-AIR FLOW



Use this work sheet to determine if you have a
conned or unconned space.
 Includes the room in which you will install
heater plus any adjoining rooms with doorless
passageways or ventilation grills between the
rooms.
AIR FOR COMbUSTION
AND VENTILATION
Continued
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free heater ____________ Btu/Hr
Gas water heater* ____________ Btu/Hr
Gas furnace ____________ Btu/Hr
Vented gas heater ____________ Btu/Hr
Gas replace logs ____________ Btu/Hr
Other gas appliances* + ___________ Btu/Hr
Total = ___________ Btu/Hr
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
Example:
Gas water heater ____________ Btu/Hr
Vent-free heater + ___________ Btu/Hr
Total = ___________ Btu/Hr
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_________
Btu/Hr (maximum the space can support)
_________
Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space
can support)
56,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a conned space
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must provide
additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconned
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building, page 8.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/Hr
size makes room unconned.
30,000
26,000
56,000