FIREPLACE INSTALLATION
Figure 22 - External Regulator with Vent
Pointing Down (Propane/LP Only)
Propane/LP Supply Tank
External
Regulator
with Vent
Pointing
Down
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" diameter or greater to allow
proper gas volume to replace.
If pipe is too small, undue loss
of volume will occur.
Installation must include an equipment shutoff

NPT tap within reach for test gauge hook up.
   
(see Figure 23).
CHECK GAS TYPE

propane/LP). If your gas supply is not the



conversion kit (see Accessories
INSTALLING GAS PIPING TO
FIREPLACE LOCATION
WARNING: A qualified
service person must connect
replace to gas supply. Follow
all local codes.
CAUTION: For propane/LP
units, never connect fireplace
directly to the propane/LP supply.
This heater requires an external
regulator (not supplied). Install
the external regulator between the
replace and propane/LP supply.
Installation Items Needed
  
have the items listed below.
external regulator (supplied by installer)
piping (check local codes)
sealant (resistant to propane/LP gas)
equipment shutoff valve *
test gauge connection *
sediment trap
 
pipe wrench
 -
tor (if allowed by local codes)
   
valve with 1/8" NPT tap is an acceptable al-
ternative to test gauge connection. Purchase
 
valve from your retailer.
    
must supply an external regulator. External
regulator will reduce incoming gas pressure.
You must reduce incoming gas pressure to
between 11" and 14" of water. If you do not
   
regulator damage could occur. Install external
regulator with vent pointing down as shown in
Figure 22. Pointing vent down protects it from

Figure 23 - Gas Connection

Equipment Shutoff Valve
with 1/8" NPT Tap*
3" Minimum
Approved
Flexible
Gas Line
Cap Pipe Tee Joint
Nipple
Sediment Trap/Drip Leg
Natural - From
Gas Meter (5.5"
W.C. to 10.5" W.C.
Pressure)
Propane/LP From
External Regulator
(11" W.C. to 14"
W.C. Pressure)

valve may be supplied with the appliance or
you can purchase it from your retailer.