Crown Boiler BSI172 Boiler User Manual


 
38
37
Troubleshooting Chart for BSI Boilers Equipped with
McDonnell & Miller #67 Low Water Cut-offs and Vent Dampers
Caution: Read page 34 before attempting to use this chart
Is there an audible
click as R8225 relay
pulls in w hen the
thermostat calls for
heat?
Does relay
pull in now ?
Vent
damper
open?
START
Thermostat
calls for heat
24 volts across
blue and yellow
wires inside
junction box?
120 volts across
black and w hite
transformer
leads?
*Pow er of f
*Blow n fuse or
tripped
breaker
*Misw ired or
loose 120 volt
connection
N
Y
* Def ective
transformer
See Note #6 on
page 34
N
Y
* Bad connection in
thermostat w iring
* Defective thermostat
* Thermostat misw ired or
misapplied
N
N
24 volts
betw een terminal # 1
on 67 LWCO and
yellow tranformer
connection?
24 volts present
betw een each
pressure limit
connection and
yellow transformer
connection?
* Boiler off on pressure limit
* Defective pressure limit
Is 24 volts
present across
brow n and
yellow leads on
R8225 relay?
Disconnect
thermostat and
temporarily jump
boiler thermostat
connections
together
* Loose
connection
betw een
transformer
and R8225
coil
* Def ective
R8225
See Note #7
on page 34
* Boiler off on low water
24 volts present
across blue lead on
R8225 and yellow
transformer leads?
* Def ective R8225
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
N