CAEN Installation
In accordance with all national and local codes a licensed
electrician must mount the enclosure. Special attention
must be made to NEC Article 110.26(A)(2) concerning
minimum work space requirements.
When choosing components to place in CAEN enclosures,
refer to the table on the previous page to ensure that the
maximum weight capacity is not exceeded. The weight of
each module is listed on the product page on the Crestron
website.
CAUTION: These enclosures house equipment that
requires air cooling. Therefore, mount in a well-ventilated
area. The ambient temperature range should be 32°F
to 104°F (0°C to 40°C). The relative humidity should
range from 0% to 90% (non-condensing). Furthermore,
allow adequate clearance in front of the vented cover
for servicing and ventilation.
NOTES: Unless otherwise indicated, the lighting system
specified in this guide is modular, requiring assembly in
the field by a licensed electrician in accordance with all
national and local codes. If you require a UL listed panel,
Crestron offers this service through its UL listed panel
shop. This includes complete in-factory system
configuration and assembly by Crestron for an additional
fee. All commercial lighting systems include factory
assembled, UL listed panels.
Install modules into the lowest available spaces and
continue toward the top of the enclosure.
Enclosures are intended for indoor use only.
When flush mounting, 5/8” drywall is preferred.
CAEN Enclosure Framing
CAEN enclosures 2X1, 4X1, and 7X1 fit between standard
wall stud spacing (16 inches on center).
CAEN 2X1, 4X1, and 7X1 Framing
CAEN enclosures 4X2 and 7x2 require framing
modification. The weight of the enclosure rests on a sill
plate, and does not distort the surrounding wallboard.