8
UV36RN/RP Vent-Free Gas Fireplaces
20007436
21¹⁄₈"
14¹⁄₂"
1/2"
36"
36"
32¹⁄₈"
14¹⁄₂"
Min.
36¹⁄₈"
T143
framing dimension
11/4/03 djt
1/2” Clearance
not Required
at This Point
2” Min. Clearance
to Mantel Leg
T143
Fig. 4 UV36 framing dimensions.
Clearances
To ensure a safe installation, the following instructions
must be carefully observed.
1. Sidewall Clearances: Clearances from the side of
the fireplace opening to any combustible wall should
not be less than 2”.
2. Ceiling Clearances: The ceiling height should not
be less than 36” from the top of the fireplace (Fig.
5a).
Mantel Clearances:
a. Mantel profile: The minimum distance above the
fireplace opening to combustible material project-
ing 1” (tile moldings, breast boards, etc.) is 13”.
Combustible material projecting 6” (a mantel
shelf, for example) requires a minimum clearance
of 20¹⁄₄” above the fireplace opening. Required
clearance varies with the amount of projection.
(Fig. 5a)
The mantel profile must fall within the cross-sec-
tion shown in Figure 5a (with standard canopy)
or Figure 5b (if a AH3342 adjustable canopy is
used).
b. With Canopy: The minimum distance above the
fireplace opening to combustible material project
-
ing 1” (tile moldings, breast boards, etc.) is 9”.
Combustible material projecting 6” (a mantel
shelf, for example) requires a minimum clearance
of 12” above the fireplace opening. Required
clearance varies with the amount of projection.
(Fig. 5b)
c. Heat resistant material: Any heat resistant mate-
rial suitable for a continuos operating temperature
of 120°C (248°F) must cover the wall surface di-
rectly above the fireplace opening and extend the
full width of the fireplace opening for a distance
of 9” above the opening of the fireplace. (Figs. 5a
and 5b)
d. Refer to Figure 6 for mantel leg clearances.
NOTE: Due to the continuous heat output of a
Vent Free Fireplace, occasional discoloration or
peeling of paint and varnish materials may be
noticed directly above the fireplace opening.
T144
standard canopy
clearances
11/4/03 djt
1"
10"
7"
4"
12"
13"
17¹⁄₄"
21¹⁄₂"
26"
Min. 36"
From Top
of Unit to
Ceiling
1"
10"
7"
4"
12"
13"
17¹⁄₄"
21¹⁄₂"
26"
Min. 36" From Top
of Unit to Ceiling
Combustible
Header
Standoff
Spacer
Ceiling*
Combustibles
Allowed in
Shaded Area
Combustible
Face Wall
Noncombus-
tible to Top of
Standoff
Canopy
Top of Screen
Frame
Fireplace
Top Face
Top of Fireplace
Opening
T144
Fig. 5a Minimum mantel clearance with standard canopy.
*Ceiling height is the minimum height of the room ceiling in front of
the fireplace measured from the top front edge of the fireplace.
Hex Head Screws
Canopy
Canopy Installation
(Top View)