Vermont Casting DVRTSB Indoor Fireplace User Manual


 
16
DVRTSB Bay Window Fireplace
10003848
STEP 2
Measure wall thickness and cut zero clearance sleeve
parts to proper length (MAXIMUM 12”/305 mm). As-
semble sleeve and attach to firestop with #8 sheet
metal screws (supplied). Install firestop assembly. (Fig.
24)
Zero clearance sleeve is only required for
combustible walls.
STEP 3
Place fireplace into position. (Fig. 25) Measure the ver
-
tical height (X) required from the base of the flue collars
to the center of the wall opening.
ZCS101
Zero Clearance Sleeve
3/11/99 djt
Max. Length 12”
(305mm)
#8 Screws (2)
#8 Screws
(2)
Adjustable Zero Clearance Sleeve
ZCS101
#8 Screws (2)
Firestop
Adjustable Zero
Clearance Sleeve
Fig. 24 Adjustable zero clearance sleeve.
X
X
FP1384
Fig. 25 Vertical height requirements.
STEP 5
Measure the horizontal length requirement including a
2” (51 mm) overlap, i.e. from the elbow to the outside
wall face plus 2” (51 mm) (or the distance required if
installing a second 90° elbow. (Fig. 26)
Always install horizontal venting on a level
plane.
STEP 6
Use appropriate length of pipe sections - telescopic or
fixed and install. The section which goes through the
wall is packaged with the starter kit, and can be cut to
suit if necessary.
Sealing vent pipe and firestop gaps with high tem-
perature sealant will restrict cold air being drawn in
around fireplace.
X
X
FP1385
Fig. 26 Horizontal length requirement.
STEP 4
Apply a bead of silicone to the inner and outer flue
collars of the fireplace and using appropriate length of
pipe section(s) attach to fireplace with three (3) screws.
Follow with the installation of the inner and outer elbow,
again secure joints as described in “Connecting Vent
Pipes”.
STEP 7
Apply high temperature sealant to 4” (100mm) and 7”
(175mm) collars or the termination one inch away from
crimped end. Guide the vent terminations 4” and 7” col-
lars into their respective vent pipes. Double check that
the vent pipes overlap the collars by 2” (50mm). Secure
the termination to the wall with screws provided and
caulk around the wall plate to weatherproof.
Support the horizontal pipes every 36” (914mm)
with metal pipe straps.
Check the fireplace to make sure that it is levelled
and properly positioned.