Vermont Casting 1450 Stove User Manual


 
13
Encore 1450 Non-Catalytic Woodburning Stove
30002425
ST253b
Encore
trim clearances
02/01 djt
C
C
A
B
D
Fireplace and Mantel Trim Clearances
Unprotected Protected
A. Mantel 38” (965 mm) 22” (559 mm)
B. Top Trim 27” (686 mm) 20” (508 mm
C. Side Trim 10” (254 mm) --
D. Side Wall 18” (457 mm) 8” (203 mm)
ST253b
Fig. 16 Maintain clearances to combustible components of
the mantelpiece.
Side
Wall
Alcove Installations
Because of their restricted air flow and heat reten-
tion characteristics, alcove installations have specific
construction requirements and special clearances. No
rear stove or chimney connector heat shields are used
in alcove installations. Bottom heat shield requirements
remain the same as for other installations.
ALCOVE INSTALLATION OF THE ENCORE IS NOT
PERMITTED IN CANADA.
Construction Requirements
The following illustrations show noncombustible ceiling
framing and maximum and minimum permitted dimen-
sions for alcove construction.
36"
Max.
48" Min.
ST502
Intrepid
Alcove floor plan
11/10/00 djt
Use recommended
floor protection
7/16” Durock®
(or equivalent)
spaced 1” off
wood studs on
noncombustible
spacers
ST502
Fig. 17 Floor plan. Sheetrock on front face butts to Durock®
(or equivalent) alcove lining.
ST503
Alcove side view
11/10/00 djt
Joist Shield
(Supplied
by Chimney
Manufac-
turer)
Metal
Stud
1” Air gap top
to bottom, on
both sides and
back wall
7/16” Durock®
(or equivalent)
Combustible
facing may
overlap metal
studs by 1”
ST503
Fig. 18 Alcove side section.