Carrier ZONEKIT4ZCAR Air Conditioner User Manual


 
Table 13—Storage Failure Errors
Error Display (Dial Position T4) must be turned on.
SF ERROR CODE DESCRIPTION SOLUTION
01 Temperature Programming Error Reprogram the scheduled temperatures.
02 Time Period Programming Error Reprogram the scheduled time periods.
03
Zone 1 Temperature Calibration Out
of Range
1. Turn selection dial to position 2.
2. Change temperature value.
3. Return selection dial to any run mode position. Valid temperature range = 30°—180°F.
04
Zone 2 Temperature Calibration Out
of Range
1. Turn selection dial to position 3.
2. Change temperature value.
3. Return selection dial to any run mode position. Valid temperature range = 30°—180°F.
05
Zone 3 Temperature Calibration Out
of Range
1. Turn selection dial to position 4.
2. Change temperature value.
3. Return selection dial to any run mode position. Valid temperature range = 30°—180°F.
06
Zone 4 Temperature Calibration Out
of Range
1. Turn selection dial to position 5.
2. Change temperature value.
3. Return selection dial to any run mode position. Valid temperature range = 30°—180°F.
07
Duct Temperature Calibration Out of
Range
1. Turn selection dial to position 6.
2. Change temperature value.
3. Return selection dial to any run mode position. Valid temperature range = 30°—180°F.
08
Outside Temperature Calibration Out
of Range
1. Turn selection dial to position 7.
2. Change temperature value.
3. Return selection dial to any run mode position. Valid temperature range = 30°—120°F.
09
Dx Coil Temperature Calibration Out
of Range
1. Turn selection dial to position 8.
2. Change temperature value.
3. Return selection dial to any run mode position. Valid temperature range = 30°—180°F.
10 LAT Error
1. Turn selection dial to position S.
2. Select variable number 6.
3. Enter a new value.
4. Return selection dial to any run mode position.
11 Device Address Error
1. Turn selection dial to position S.
2. Verify correct address of the 4 zone controller is as shown in the Programming and Operation
Section.
3. Verify smart sensor address(es) are as shown in the Programming and Operation Section.
12 Configuration Error
1. Turn selection dial to position T2, T11, T12, T18, T20, T22, and T24.
2. Check and correct the configuration.
3. Return selection dial to any run mode position.
13 Configuration Error
1. Turn selection dial to position T4, T5, T6, T13, and T17.
2. Check and correct the configuration.
3. Return selection dial to any run mode position.
14 Configuration Error
1. Turn selection dial to position T7, T8, T9, T10, T19, T21, T23, and T25.
2. Check and correct the configuration.
3. Return selection dial to any run mode position.
15 Configuration Error
1. Turn selection dial to position T26 and T27.
2. Check and correct the configuration.
3. Return selection dial to any run mode position.
16 Configuration Error Push HOLD button on/off.
17 Current Setpoints
1. Turn the error display T4 off.
2. Change any setpoint.
3. Turn the error display T4 on.
4. Return selection dial to any run mode position.
18 Vacation Setpoints
1. Turn the error display T4 off.
2. Turn the selection dial to Vacation.
3. Change any setpoint.
4. Turn the error display T4 on.
5. Return selection dial to any run mode position.
19
Maximum/Minimum Temperature Set-
points
1. Turn selection dial to position S.
2. Change the maximum cooling setpoint (S2). Must be outside 14° range.
3. Change the minimum heating setpoint (S3). Must be outside 14° range.
4. Return selection dial to any run mode position.
20
Maximum/Minimum Damper Ventila-
tion
1. Turn the selection dial to position S.
2. Change the maximum damper position (S4). Default = 15.
3. Change the vent damper position (S5). Default = 0.
4. Return selection dial to any run mode position.
21 Bypass Damper Total
1. Turn the selection dial to position 1.
2. Re-program bypass damper pressure relief limit according to instructions on Programming Sec-
tion.
22 Baud Rate
1. Turn selection dial to position T1.
2. Toggle the baud rate twice (T3).
3. Return selection dial to any run mode position.
23 Dual Fuel Trip Temperature Error
1. Turn selection dial to position S7.
2. Change the value.
3. Return selection dial to any run mode position.
24 Base Temperatures Error
1. Turn selection dial to position 9.
2. Set base temperatures. Do not overlap with 14° maximum cooling/minimum heating set point
range.
3. Return selection dial to any run mode position.
20