Carrier HUMCCLFP1025-A Humidifier User Manual


 
7. Saddle valve assembly with adapter
8. Four sheet metal screws
9. Foam tape
10. Noise suppressor (use for water pressure over 60 psi)
11. Worm clamp for field-supplied drain tube
12. Humidifier maintenance instruction sticker
13. Carrier logo label
Step 2— Select Location (See Fig. 7.)
Humidifier must be installed on supply plenum only. If furnace has
air conditioning coil, be sure humidifier does not interfere with coil
ends. Remember to provide clearance for maintenance and evapo-
rator pad removal.
To reverse pad access from right to the left side:
1. Remove side door and media pad assembly.
2. Remove 4 screws and separate top assembly from lower
mounting base. (See Fig. 8.)
3. Rotate lower mounting base 180 degrees, so side access door
is now on left.
4. Snap together top assembly to mounting base and reinstall
screws.
5. Replace media pad assembly (with distributor reservoir up)
and side access door.
When re-installing media pad assembly into plastic housing,
insure the assembly drain stub aligns into the drain outlet
located in bottom of humidifier. Unit can leak if drain stub
does not align with drain outlet. (See Fig. 9.)
IMPORTANT: Make sure front housing assembly with electrical
cord is facing down.
Step 3—Prepare Plenum Opening (See Fig. 2.)
1. Use template for marking humidifier opening.
2. Tape in place on plenum making sure template is level.
IMPORTANT: For humidifier to operate properly it must be level
and mounted on a vertical surface.
3. Drill four 1/8-in. holes in plenum.
4. Cut opening in plenum using heavy solid lines on template as
a guide.
Step 4—Mount the Humidifier
1. Attach foam tape to back of mounting flange (exclude the
off-set edge).
2. Hook off-set edge over opening cut in plenum.
3. Place humidifier in plenum aligning screw holes with flange.
4. Align, level, and tighten all screws for air tight seal.
Step 5—Install Drain Line
1. Use 5/8-in. vinyl tubing (field supplied) to connect drain on
bottom of humidifier housing to an open drain.
2. Use clamp to hold drain tubing in position over drain fitting
outlet.
Unit may leak if drain tubing is misapplied. Do not insert
tubing inside of drain fitting outlet.
3. Make sure line is free of traps due to sagging and has
sufficient pitch to drain.
Fig. 7—Installation of HUMCCSFP1016-A--
Fan-Type Humidifier
A97098
VERTICAL HORIZONTAL
HORIZONTAL
"N" COIL
Fig. 8—Reversing Door Access
on HUMCCSFP1016-A--
A96049
Fig. 9—Media Pad Assembly Installation
A97108
MEDIA PAD
ASSEMBLY
HOUSING
ENCLOSURE
DRAIN OUTLET
DRAIN
OUTLET
VINYL DRAIN
TUBING
5