Carrier 50XT Heat Pump User Manual


 
33
ELECTRICAL DATA
UNIT SIZE
V--PH--HZ
VOLTAGE
RANGE
COMPRESSOR OFM
FLA
IFM
FLA
ELECTRIC HEAT
SINGLE POINT POWER
SUPPLY
NOMINAL
FLA MCA MOCP
MIN MAX RLA LRA kW*
024 208/230--1--60 187 253 15.3 52.0 0.9 4.3
-- / -- -- / -- 24.3/24.3 35/35
3.8/5.0 18.1/20.8 46.9/50.3 50/60
5.4/7.2 26.0/30.0 56.8/61.8 60/70
7.5/10.0 36.1/41.7 69.4/76.4 70/80
030 208/230--1--60 187 253 16.8 70.0 0.9 4.3
-- / -- -- / -- 26.2/26.2 40/40
3.8/5.0 18.1/20.8 48.7/52.2 50/60
5.4/7.2 26.0/30.0 58.7/63.7 60/70
7.5/10.0 36.1/41.7 71.3/78.3 80/80
11.3/15.0 54.2/62.5 93.9/104.3 100/110
036 208/230--1--60 187 253 16.7 82.0 0.9 6.8
-- / -- -- / -- 28.6/28.6 45/45
3.8/5.0 18.1/20.8 51.2/54.6 60/60
5.4/7.2 26.0/30.0 61.1/66.1 70/70
7.5/10.0 36.1/41.7 73.7/80.7 80/90
11.3/15.0 54.2/62.5 96.3/106.7 100/110
042 208/230--1--60 187 253 21.8 96.0 0.9 6.8
-- / -- -- / -- 34.9/34.9 50/50
3.8/5.0 18.1/20.8 57.5/60.9 60/70
5.4/7.2 26.0/30.0 67.4/72.4 70/80
7.5/10.0 36.1/41.7 80.0/87.0 90/90
11.3/15.0 54.2/62.5 102.6/113.0 110/125
15.0/20.0 72.2/83.3 125.2/139.1 150/150
048 208/230--1--60 187 253 27.8 96.0 1.5 6.8
-- / -- -- / -- 43.1/43.1 60/60
3.8/5.0 18.1/20.8 65.7/69.1 70/70
5.4/7.2 26.0/30.0 75.6/80.6 80/90
7.5/10.0 36.1/41.7 88.2/95.2 90/100
11.3/15.0 54.2/62.5 110.8/121.2 125/125
15.0/20.0 72.2/83.3 133.4/147.3 150/150
060 208/230--1--60 187 253 27.3 118.0 1.9 9.1
-- / -- -- / -- 45.2/45.2 60/60
3.8/5.0 18.1/20.8 67.7/71.2 70/80
5.4/7.2 26.0/30.0 77.6/82.7 80/90
7.5/10.0 36.1/41.7 90.3/97.2 100/110
11.3/15.0 54.2/62.5 112.9/123.3 125/125
15.0/20.0 72.2/83.3 135.4/149.3 150/150
*Heater capacity (kW) based on heater voltage of 208v & 240v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
LEGEND
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
®