Carrier 50XT Heat Pump User Manual


 
15
PERFORMANCE DATA--STANDARD ECM INDOOR MOTOR
Heating Capacity
50XT030 High
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES _F(_C)
--10 (--23.3) 0 (--17.7) 10 (--12.2) 17 (--8.3) 20 (--6.6)
EDB
_F
(_C)
CFM
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Total Integ Total Integ Total Integ Total Integ Total Integ
60
(15.6)
875 7.07 6.51 1.56 9.35 8.60 1.64 12.08 11.09 1.72 14.34 13.07 1.78 15.42 13.99 1.81
1000 7.16 6.59 1.56 9.46 8.70 1.64 12.23 11.23 1.71 14.51 13.23 1.77 15.61 14.16 1.79
70
(21.1)
875 6.74 6.20 1.73 9.00 8.28 1.82 11.66 10.70 1.91 13.82 12.60 1.97 14.85 13.46 2.00
1000 6.84 6.29 1.73 9.12 8.39 1.82 11.80 10.83 1.90 14.00 12.76 1.95 15.04 13.64 1.98
80
(26.7)
875 6.31 5.81 1.90 8.56 7.88 2.00 11.20 10.28 2.10 13.30 12.13 2.17 14.28 12.95 2.20
1000 6.42 5.91 1.90 8.69 8.00 2.00 11.35 10.42 2.09 13.48 12.29 2.15 14.46 13.11 2.18
50XT030 High Con’t.
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES _F(_C)
30 (--1.1) 40 (4.4) 47 (8.3) 50 (10) 60 (15.5)
EDB
_F
(_C)
CFM
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Total Integ Total Integ Total Integ Total Integ Total Integ
60
(15.6)
875 19.48 17.07 1.91 24.32 24.32 2.04 28.09 28.09 2.08 29.61 29.61 2.12 35.99 35.99 2.18
1000 19.75 17.31 1.89 24.63 24.63 2.02 28.28 28.28 2.15 30.05 30.05 2.19 36.32 36.32 2.32
70
(21.1)
875 18.76 16.44 2.11 23.39 23.39 2.23 27.23 27.23 2.34 29.07 29.07 2.40 35.34 35.34 2.46
1000 19.03 16.67 2.08 23.75 23.75 2.20 27.60 27.60 2.31 29.24 29.24 2.34 35.85 35.85 2.54
80
(26.7)
875 18.00 15.77 2.31 22.48 22.48 2.44 26.17 26.17 2.56 27.94 27.94 2.62 34.42 34.42 2.70
1000 18.32 16.05 2.28 22.83 22.83 2.40 26.59 26.59 2.51 28.38 28.38 2.57 34.50 34.50 2.82
LEGEND
Cap.— Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db —DryBulb
kW — Total Power Input (Includes Compressor Motor Power Input Outdoor-- Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
50XT