PERFORMANCE DATA--STANDARD ECM INDOOR MOTOR
Heating Capacity
50XT042 High
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES _F(_C)
--10 (--23.3) 0 (--17.7) 10 (--12.2) 17 (--8.3) 20 (--6.6)
EDB
_F
(_C)
CFM
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Total Integ Total Integ Total Integ Total Integ Total Integ
60
(15.6)
1225 10.65 9.80 2.06 13.99 12.87 2.19 17.85 16.39 2.32 21.02 19.17 2.41 22.53 20.43 2.46
1400 10.79 9.92 2.08 14.15 13.02 2.20 18.04 16.56 2.32 21.26 19.39 2.41 22.79 20.67 2.45
70
(21.1)
1225 10.16 9.34 2.28 13.49 12.42 2.42 17.32 15.89 2.55 20.37 18.58 2.66 21.80 19.77 2.70
1400 10.32 9.49 2.29 13.66 12.57 2.42 17.52 16.08 2.55 20.60 18.78 2.65 22.06 20.01 2.69
80
(26.7)
1225 9.53 8.77 2.49 12.89 11.86 2.64 16.69 15.32 2.80 19.70 17.96 2.91 21.10 19.14 2.96
1400 9.69 8.92 2.51 13.07 12.03 2.65 16.90 15.51 2.80 19.94 18.18 2.90 21.36 19.37 2.94
50XT042 High Con’t.
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES _F(_C)
30 (--1.1) 40 (4.4) 47 (8.3) 50 (10) 60 (15.5)
EDB
_F
(_C)
CFM
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Capacity
MBtuh
Total
System
KW
Total Integ Total Integ Total Integ Total Integ Total Integ
60
(15.6)
1225 28.26 24.77 2.62 35.01 35.01 2.81 40.36 40.36 2.97 42.96 42.96 3.05 51.37 51.37 3.25
1400 28.60 25.06 2.60 35.38 35.38 2.79 40.37 40.37 2.91 43.00 43.00 2.96 51.50 51.50 3.19
70
(21.1)
1225 27.38 23.99 2.87 33.83 33.83 3.06 39.05 39.05 3.22 41.60 41.60 3.31 50.54 50.54 3.54
1400 27.71 24.28 2.85 34.27 34.27 3.03 39.50 39.50 3.20 41.96 41.96 3.27 50.80 50.80 3.48
80
(26.7)
1225 26.37 23.10 3.13 32.67 32.67 3.34 37.72 37.72 3.50 40.19 40.19 3.59 49.42 49.42 3.92
1400 26.72 23.41 3.11 33.12 33.12 3.30 38.23 38.23 3.46 40.71 40.71 3.55 49.70 49.70 3.78
LEGEND
Cap.— Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db —DryBulb
kW — Total Power Input (Includes Compressor Motor Power Input Outdoor-- Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
50XT