Carrier 50RHC Heat Pump User Manual


 
25
Table 6 — 50RHR,RVR Electrical Data
LEGEND
*Size 006 is available in 50RHR units only.
50RHR,RVR
UNITS
VOLTS-PHASE
60 Hz
VOLTAGE
MIN/MAX
COMPRESSOR FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE/HACR
RLA LRA
006*
208/230-1 197/254 2.9 17.7 0.40 3.3 4.0 15
265-1 239/292 2.5 15.0 0.35 2.8 3.5 15
009
208/230-1 197/254 3.9 22.2 0.80 4.7 5.7 15
265-1 239/292 3.3 18.8 0.90 4.2 5.0 15
012
208/230-1 197/254 5.3 27.9 0.80 6.1 7.5 15
265-1 239/292 4.2 22.2 0.90 5.1 6.2 15
015
208/230-1 197/254 5.9 29.0 1.00 6.9 8.4 15
265-1 239/292 5.4 27.0 0.86 6.3 7.7 15
019
208/230-1 197/254 7.9 48.3 1.10 9.0 11.0 15
265-1 239/292 7.1 41.0 0.90 8.0 9.7 15
024
208/230-1 197/254 8.7 48.3 1.30 10.0 12.1 20
265-1 239/292 8.3 47.0 1.58 9.9 12.0 20
208/230-3 197/254 6.0 50.0 1.30 7.3 8.8 15
460-3 414/506 3.2 25.0 0.85 4.1 4.9 15
030
208/230-1 197/254 11.2 60.0 1.90 13.1 15.9 25
265-1 239/292 10.3 58.0 1.66 11.9 14.5 20
208/230-3 197/254 6.4 50.0 1.90 8.3 9.9 15
460-3 414/506 3.2 25.0 1.00 4.2 5.0 15
036
208/230-1 197/254 14.1 84.0 3.00 17.1 20.6 30
265-1 239/292 13.5 83.0 2.70 16.2 19.5 30
208/230-3 197/254 8.2 63.4 3.00 11.2 13.3 20
460-3 414/506 4.1 36.0 1.70 5.8 6.8 15
042
208/230-1 197/254 16.2 96.0 3.00 19.2 23.2 35
208/230-3 197/254 10.3 75.0 3.00 13.3 15.8 25
460-3 414/506 4.3 40.0 1.70 6.0 7.1 15
575-3 518/633 3.7 31.0 1.50 5.2 6.1 15
048
208/230-1 197/254 18.3 102.0 3.40 21.7 26.2 40
208/230-3 197/254 12.6 91.0 3.40 16.0 19.2 30
460-3 414/506 5.7 42.0 1.80 7.5 8.9 15
575-3 518/633 4.7 39.0 1.60 6.3 7.5 15
060
208/230-1 197/254 25.6 170.0 4.30 29.9 36.4 60
208/230-3 197/254 14.7 124.0 4.30 19.0 22.7 35
460-3 414/506 7.4 59.6 2.50 9.9 11.8 15
575-3 518/633 5.9 49.4 2.20 8.1 9.8 15
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
LRA Locked Rotor Amps
RLA Rated Load Amps