Single Point Boxes and Supplementary Fuse
When the unit MOCP device value exceeds 60--A,
unit--mounted supplementary fuses are required for each
heater circuit. These fuses are included in accessory
Single Point Boxes, with power distribution and fuse
blocks. The single point box will be installed directly
under the unit control box, just to the left of the partition
separating the indoor section (with electric heaters) from
the outdoor section. The Single Point Box has a hinged
access cover. See Fig. 26. The Single Point Box also
includes pigtails to complete the wiring between the
Single Point Box and the unit’s main control box
terminals. Refer to the accessory heater and Single Point
Box installation instructions for details on tap
connections.
A
L
L
I
E
D
P
A
M
O
D
E
L
N
O
.
ER
I
A
L
N
O.
C
O
R
P
.
11
13
21
23
O
D
2
2
.
2
3
1
2
3
ISTED
AI
R
NDITIONING
UIP
ACCESS
3
4
6
N
.
P
/
N
2-
5
6
10-
4
REV
1
1
13
2
1
2
3
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
FOAM
BUSHING
DRIP BOOT
BRACKET
MOUNTING
SCREWS
HEATER
RELAYS
POWER
WIRES
HEATER
MOUNTING
SCREWS
C08136
Fig. 26 -- Typical Single Point Installation
All fuses on 50HCQ units are 60--A. (Note that all heaters
are qualified for use with a 60--A fuse, regardless of actual
heater ampacity, so only 60--A fuses are necessary.)
Single Point Boxes without Fuses: Refer to accessory
heater and Single Point Box installation instructions for
details on tap connections.
Low--Voltage Control Connections: Run the low--voltage
control leads from the heater module(s) -- VIO and BRN
(two of each if two modules are installed; identify for
Module #1) -- to the 4--pole terminal board TB4 located on
the heater bulkhead to the left of Heater #1. Connect the
VIO leads from Heater #1 and Heater #2 to terminal
TB4--1. Connect the BRN leads to terminal TB4--3. See
Fig. 27.
DEFROST
BOARD
ORN
BRN
Field
Connections
E-HEAT
P3-3
13
ORN BRN
VIO BRN BRN
VIO
TB4
VIO HR2
HR1
BRN
VIO BRN
Elec Htr
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
C09013
Fig. 27 -- Accessory Electric Heater Control Connections
50HCQA