Carrier 50GL 024-060 Air Conditioner User Manual


 
Table 13—48GP & 48JZ Gas Heating ICM Airflow
Small Cabinet
EASY SELECT™
BOARD SETTING (CFM)
700 800 1100 1250
Unit
Size
External
Static
Pressure
0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0
Gas Heat Size
024
040 –––855770710––––––
060 ––––––1020 890 835
030
040 –––880840805––––––
060 ––––––1030 970 910
036
060 ––––––1035 995 955
090 –––––––––1170 1110 1025
Table 14—48GP & 48JZ Gas Heating ICM Airflow
Large Cabinet
EASY SELECT™
BOARD SETTING (CFM)
1000 1250 1600 1750 1800
Unit
Size
External
Static
Pressure
0.0–1.0 0.0–1.0 0.0–1.0 0.0–1.0 0.0–1.0
Gas Heat Size
042
060 1000 ––––
090 1250
048
090 1250
115 1600
130 1750
060
090 1250
115 1600
130 ––––1800
Table 15—48GP & 48JZ ICM Air Flow vs. Temperature Rise Chart
UNIT
COOLING
SIZE
RATED GAS
INPUT RATE
(X 1000)
AIRFLOW SETTING
EASY SELECT™
(SCFM)
CALCULATED
TEMPERATURE
RISE
MIN.
TEMP
RISE
MAX
TEMP
RISE
MAX
DISCH.
TEMP
48GP
&
48JZ
024
40 800 36.5 20 50 175
60
(48GP Only)
1100 40 35 65 165
030
40 800 36.5 20 50 175
60 1100 40 35 65 165
036
60 1100 40 25 55 165
90 1200 54 45 75 175
042
60 1000 44 20 50 165
90 1250 53 35 65 170
048
90 1250 53 25 55 165
115 1600 53 35 65 170
130 1750 54 40 70 175
060
90 1600 41 25 55 155
115 1600 53 35 65 170
130 1800 53 40 70 175
25