Table 12 – Troubleshooting Guide–Heating
SYMPTOM CAUSE REMEDY
Burners will not ignite
Water in gas line Drain. Installdrip leg.
No power to furnace Check power supply fuses, wiring or circuit breaker.
No 24--v power supply to control circuit
Check transformer.
NOTE: Some transformers have internal over--current protection
that requires a cool--down period to reset.
Mis--wired or loose connections Check all wiring and wire nut connections
Misaligned spark electrodes
Check flame ignition and sense electrode positioning.
Adjust as necessary.
No gas at main burners
1. Check gas line for air. Purge as necessary. NOTE: After purging
gas line of air, wait at least 5 minutes for any gas to dissipate be-
fore attempting to light unit.
2. Check gas valve.
Inadequate heating
Dirty air filter Clean or replace filter as necessary
Gas input to furnace too low Check gas pressure at manifold match with that on unit nameplate
Unit undersized for application Replace with proper unit or add additional unit
Restricted airflow Clean or replace filter. Remove any restriction.
Limitswitch cycles mainburners
Check rotation of blower, temperature rise of unit. Adjust as neces-
sary.
Poor flame characteristics
Incomplete combustion results in: Aldehyde odors,
carbon monoxide, sooting flame, floating flame
1. Tighten allscrews around burner compartment
2. Cracked heat exchanger. Replace.
3. Unit over--fired. Reduce input (change orifices or adjust gas line
or manifold pressure).
4. Check burner alignment.
5. Inspect heat exchanger for blockage. Clean as necessary.
Table 13 – Troubleshooting Guide–LED Error Codes
SYMPTOM CAUSE REMEDY
No Power or Hardware fail-
ure
(LEDOFF)
Loss of power to control module (IGC)*.
Check 5--amp fuse son IGC*, power to unit, 24--v circuit breaker,
and transformer. Units without a 24--v circuit breaker have an
internal overload in the 24--v transformer. If the overload trips,
allow 10 minutes for automatic reset.
Limit switch faults
(LED 2 flashes)
High temperature limit switch is open.
Check the operation of the indoor (evaporator) fan motor. Ensure
that the supply--air temperature rise is in accordance with the
range on the unit nameplate. Clean or replace filters.
Flame sense fault
(LED 3 flashes)
The IGC* sensed flame that should not be present. Reset unit. If problem persists, replace control board.
4 consecutive limit switch
faults
(LED 4 flashes)
Inadequate airflow to unit.
Check the operation of the indoor (evaporator) fan motor and that
supply--air temperature rise agrees with range on unit nameplate
information.
Ignition lockout
(LED 5 flashes)
Unit unsuccessfully attempted ignition for 15 minutes.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that fame sense and ignition wires are properly terminated.
Verify that unit is obtaining proper amount of gas.
Pressure Switch Fault
(LED 6 flashes)
Open pressureswitch.
Verify wiring connections to pressure switch and inducer motor.
Verify pressure switch hose is tightly connected to both inducer
housing and pressure switch. Verify inducer wheel is properly
attached to inducer motor shaft. Verify inducer motor shaft is turn-
ing.
Rollout switch fault
(LED 7 flashes)
Rollout switch has opened.
Rollout switch will automatically reset, but IGC* will continue to
lockout unit. Check gas valve operation. Ensure that induced--draft
blower wheel is properly secured to motor shaft. Inspect heat
exchanger. Reset unit at unit disconnect.
Internal control fault
(LED 8 flashes)
Microprocessor has sensed an error in the software
or hardware.
If error code is not cleared by resetting unit power, replace the
IGC*.
Temporary 1 hr auto reset
(LED 9 flashes)
Electrical interference impeding IGC software
Reset 24--v. to control board or turn thermostat off, then on again.
Fault will automatically reset itself in one (1) hour.
*WARNING : If the IGC must be replaced, be sureto groundyourself to dissipate any electrical charge thatmy bepresentbefore handlingnew control
board.Th e IGC is sensitiveto static electricity andmy be damagedif the necessary precautions aren ot taken.
IMPORTANT: Refer to Table 11---Troubleshooting Guide---Heating for additional troubleshooting analysis.