Fig. 26 -- Typical Heat Pump Operation, Cooling Mode
COMPRESSOR
ACCUMULATOR
OUTDOOR COIL
INDOOR COIL
LCS
LEGEND
HPS – High Pressure Switch
LCS – Loss of Charge Switch
Accurater
®
Metering De vice
Arrow indicates direction of flo w
TXV in Bypass
Position
Metering
Position
HP S
C03012
Fig. 27 -- Typical Heat Pump Operation, Heating Mode
UNIT OPERATION AND SAFETY HAZARD
Failure to followthis warning could resultin personalinjury
or equipment damage.
This system uses Puron (R--410A) refrigerant which has
higher operating pressures than R--22 and other refrigerants.
No other refrigerant may be used in this system. Gauge set,
hoses,andrecoverysystemmustbedesignedtohandlePuron.
If you are unsure, consult the equipment manufacturer.
WARNING
!
Refrigerant System
This information covers the refrigerant system of the 48EZ--A,
including the compressor oil needed, servicing systems on roofs
containing synthetic materials, the filter drier and refrigerant
charging.
Compressor Oil
If additional oil is needed use Uniqema RL32--3MAF. If this oil is
not available, use Copeland Ultra 32CC or Mobil Artic EAL22CC.
This oil is extremely hygroscopic, meaning it absorbs water
readily. POE oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Take all necessary
precautions to avoid exposure of the oil to the atmosphere.