Carrier 40QA024-060 Air Conditioner User Manual


 
13
Step 8 — Make Connections Between Indoor
and Outdoor Units —
The thermostat is wired between
the indoor and outdoor units to make the system complete.
CHECK ACCURATER METERING DEVICE — The cor-
rect AccuRater (bypass type) refrigerant control is required for
system capacity optimization. An AccuRater device
(see Fig. 19) is supplied with the outdoor unit. Refer to
Tables 4A-4C to determine the correct AccuRater piston size
and charge combination required for the condenser/evaporator
system being installed.
Piston style as shown in Fig. 19 is shipped with the unit.
Do not interchange components between the AccuRater device
types.
COOLING ONLY SYSTEMS — The following connec-
tions must be made to the outdoor unit for it to operate as a sys-
tem with the indoor unit:
Route 2 wires of field-supplied 18-gage AWG (American
Wire Gage) thermostat cable between the low-voltage terminal
block of the fan coil unit and the blue and brown low-voltage
wires in the outdoor unit low voltage terminal block. Connect
the wires Y1 to Y and C to C. See Fig. 19.
HEAT PUMP SYSTEMS — The following connections
must be made to the outdoor unit for it to operate as a system
with the indoor unit:
Route 5 wires of field-supplied 18-gage AWG thermostat
cable between the low-voltage terminal block of the fan coil
and the outdoor unit low-voltage terminal block. Connect Y1
to Y, R to R, O to O, W2 to W2, and C to C with the wires. See
Fig. 20.
The heat pump unit uses a timed defrost method. The timed
defrost can be field set for 30, 50, or 90 minutes. The timed de-
frost is factory set for 90 minutes.
LEGEND
ASM Air Sweep Motor
ASR Air Sweep Relay
EQUIP GND Equipment Ground
FL Fuse Link
FPT Freeze Protection Thermostat
HP Heat Pump
HR Heater Relay
HTR Heater
HTT Heater Temp. Thermostat
IFM Indoor-Fan Motor
NEC National Electrical Code
PL Plug
TB Terminal Board
TRAN Transformer
Terminal (Marked)
Terminal (Unmarked)
Splice
Terminal Block
Factory Wiring
Field Power Wiring
Field Control Wiring
Printed Circuit Board
Accessory or Optional Wiring
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Wire in accordance with NEC and local codes.
3. Transformer is thermally protected and will reset automatically.
4. Indoor-fan motor(s) are inherently thermally protected.
Fig. 17 — Control Circuit Connections Arrangement